PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
58
If a wrong or no login is entered, you will only have access to the Login, Filter
Operation and Configuration icons.
Click on the Hardware set-up icon.
In the hardware set-up window, you will have to specify:
? ?
The network frequency
? ?
The grid nominal voltage
? ?
The number of modules
? ?
The three lines CT ratio
Click on ‘apply’ to validate.
9.4.2. With the PQF-Manager
The 3 levels of the PQF-Manager are accessible from the window “Main
menu”.
To enter the “Main menu” window, press MENU.
Level 1 is for consulting, level 2 for filter programming and level 3 for
commissioning.
Select level 3 by pressing once the ? key.
Then press OK and enter the appropriate password for level 3.
The LED ‘SET’ will switch on.
In the hardware set-up window, you will have to specify:
? ?
The network frequency
? ?
The grid nominal voltage
? ?
The number of modules
? ?
The three lines CT ratio
MAIN MENU
Level 1
Level 2
? Level 3?
Summary of Contents for PQFA
Page 1: ...Instructions Manual PQFA Power Quality Filter ABB Jumet ...
Page 19: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 19 Master cubicle view Zoom on next page ...
Page 20: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 20 ...
Page 21: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 21 Control rack details ...
Page 22: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 22 Master cubicle door view ...
Page 24: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 24 ...
Page 25: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 25 Slave cubicle door view ...
Page 28: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 28 ...