PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
93
Error
code
Error message
Possible causes
Actions
4
DC overvoltage DC voltage on DC bus
reaches unacceptable
levels
? ?
Check DC capacitors
? ?
Inspect
?
15V power
supply (U100)
? ?
Inspect internal
current sensor
(B101/102/103)
? ?
Inspect visually DC
voltage divider and
wiring
5
Connection
fault
? ?
Flat cable between
the control rack and
IGBT driver is
disconnected or
wrongly connected.
? ?
Module number
setting on board
A112 does not
correspond to the
number of modules
really present.
? ?
The jumpers on the
last domino board
are missing or are on
the wrong domino.
? ?
Check flat cable
connections
? ?
Verify that only the
domino board of the
last power module is
fitted with jumpers
? ?
Check the number of
modules set on the
controller board A112
6
Power supply
fault
One of the auxiliary
power supplies is out of
service.
? ?
Check that no red
LED is on the control
rack (except LED 3 of
A111). If yes, call
your ABB service
provider.
? ?
Check fuses of power
supplies
7
Control board
fault
The microcontroller is
not working properly.
Contact immediately
your ABB service
provider.
8
CAN bus fault
The internal
communication bus of
the PQFA is not working
properly.
Contact immediately
your ABB service
provider.
16
DSP pgm
corrupted
DSP program corrupted
Contact immediately
your ABB service
provider.
32
Watchdog
timeout
Software in
unpredictable state.
Contact immediately
your ABB service
provider.
Summary of Contents for PQFA
Page 1: ...Instructions Manual PQFA Power Quality Filter ABB Jumet ...
Page 19: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 19 Master cubicle view Zoom on next page ...
Page 20: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 20 ...
Page 21: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 21 Control rack details ...
Page 22: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 22 Master cubicle door view ...
Page 24: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 24 ...
Page 25: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 25 Slave cubicle door view ...
Page 28: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 28 ...