5. Mechanical installation
The PQFA is suitable for indoor installation, on firm foundations, in a well-
ventilated area without dust and excessive aggressive gases where the
ambient parameters do not exceed the following values:
40°C max;
30°C (average temperature) over 24 hours;
Minimum temperature: +5 °c
Humidity less than 95% RH non-condensing
Altitude: max. 1000m without derating.
For units with nominal voltage above 415V, the rear side of the cubicles must
be located at least at 100mm from the wall as represented in the sketch
hereunder.
PQFA cubicles have standard dimensions of 800 x 600 x 2150 mm (width x
depth x height).
Each cubicle may contain one or two power modules and is fitted with its own
bottom cable entry and breaker.
For systems with more than 2 power modules, cubicles are installed on a
common base of 100-mm height. Standard dimensions for PQFA with up to 6
power modules are shown on page 26.
PQFA#1
PQFA#2
PQFA#1
PQFA#2
At least 100mm spacing must be provided between PQFA rear side and wall
Summary of Contents for PQFA
Page 1: ...Instructions Manual PQFA Power Quality Filter ABB Jumet ...
Page 19: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 19 Master cubicle view Zoom on next page ...
Page 20: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 20 ...
Page 21: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 21 Control rack details ...
Page 22: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 22 Master cubicle door view ...
Page 24: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 24 ...
Page 25: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 25 Slave cubicle door view ...
Page 28: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 28 ...