Maintenance 141
11
Maintenance
What this chapter contains
This chapter contains preventive maintenance instructions.
Safety
WARNING!
Read the
instructions on the first pages of this manual
before performing any maintenance on the equipment. Ignoring the safety
instructions can cause injury or death.
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Maintenance
Interval
Instruction
Capacitor reforming
Every year of storage
See
Heat sink temperature
check and cleaning
Depends on the dustiness of the
environment (every 6 to 12 months)
See
Cooling fan change
Every 6 years
if the ambient
temperature does not exceed 45 °C
(113 °F).
Every 3 years
if the ambient
temperature is higher than 45 °C
(113 °F).