Fault tracing 139
Controller errors
Code
Error
Cause
What to do
30001
Controller
over-temperature
(_ecOVER_TEMPERATU
RE)
The drive has detected it is
dangerously hot.
Check the drive ambient conditions allow
for sufficient cooling.
Note: TEMPERATURE will return the
current temperature, in degrees Celsius,
from the drive's internal temperature
sensor. If the temperature exceeds the
predefined TEMPERATURELIMITFATAL
value (model dependent), then an
overtemperature trip will be caused.
TEMPERATURELIMITFATAL for each
drive is;
e190 3A is 80°C,
e190 6A and 9A is 75°C
30005
FPGA failed to initialise
(_ecFPGA_INITIALISATI
ON_ERROR)
The controller FPGA has failed to
initialize. If this error is received
Power cycle. If Error Persists Replace the
Drive
30007
Error accessing non-
volatile memory
(_ecNON_VOL_MEMOR
Y_FAILURE)
Unable to access non-volatile
memory.
Power cycle. If Error Persists Replace the
Drive
30008
Error applying parameter
value
(_ecPARAM_ERROR)
Errors have occurred during a
parameter table download or
during startup. Some of the
parameters could not be applied
correctly. See the Error Log for
details of the failures. The
controller's status display will
flash only 'E', and will not be
followed with the usual error code
digits.
This Error is most commonly ascociated
with either a parameter file (.ptx) issue. It is
a common problem if the parameter file is
generated from an older firmware version
with either different parameters or different
parameter limits. Read the Error log for
specific guidance on the effected
parameters.
30009
General internal controller
error
(_ecINTERNAL_ERROR)
An internal error has occurred.
Read parameter failed
Power cycle. If Error Persists Replace the
Drive
30010
Fan is not operating
correctly (_ecFAN_LOSS)
The drive has detected that an
internal cooling fan has failed.
Check the bottom of the drive to
determine that the fan inlets are not
blocked and the fan is rotating. If the drive
fan does not turn, the general is the fan
hardware failure, need to replace the fan.
30029
Controller under-
temperature
(_ecUNDER_TEMPERAT
URE)
The controller has detected an
ambient temperature lower than -
5 °C.
The ambient temperature must be
increased before the drive can be enabled.
Summary of Contents for MicroFlex e190
Page 1: ...ABB motion control User s manual MicroFlex e190 servo drive ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 26: ...26 Introduction to the manual ...
Page 90: ...90 Electrical installation input output ...
Page 146: ...146 Maintenance ...
Page 178: ...178 Resistor braking ...
Page 186: ...186 Accessories ...
Page 208: ...208 Appendix Safe Torque Off STO ...