8 Trouble Shooting
Product Manual, Control Cabinet IRC5P
183
8.3 Fault Symptoms and Malfunctions
8.3.9 No Voltage in Service Outlet
Description
Some controllers are fitted with service voltage outlet sockets, and this information
applies to these modules only.
No voltage is available in the controller service outlet for powering external service
equipment.
Consequences
Equipment connected to the controller service outlet does not work.
Probable Causes
The symptom may be caused by (the causes are listed in order of probability):
•
Blown fuse, FU2 (230VAC) or FU3 (115VAC).
•
Mains power supply loss.
•
Transformers incorrectly connected.
Recommended Actions
Step Action
Comment
1
Make sure the fuse is not blown.
Make sure any equipment connected to
the service outlet does not consume too
much power, causing the fuse to blow.
2
Make sure the power supply to the robot
system is within specifications.
Refer to the plant documentation for
voltage values.
3
Make sure the transformer supply for the outlet
is correctly connected.
See transformer wiring diagram under
‘Mains Transformer’ in ‘Unit Description,
IRC5P’..