8 Trouble Shooting
8.3 Fault Symptoms and Malfunctions
178
Product Manual, Control Cabinet IRC5P
8.3.4 Controller Dead
Description
The robot controller is completely or intermittently ‘dead’.
No indicators are lit and no operation is possible.
Consequences
The system can not be operated.
Possible Causes
The symptom may be caused by (the causes are listed in order of probability):
•
The controller is not connected to the mains power supply.
•
The main transformer is malfunctioning or not connected correctly.
•
The mains overload protection (FR1) may have tripped.
Recommended Actions
Step Action
Comment
1
Make sure the mains power supply in the shop
is working and that the voltage level matches
that of the controller requirement.
The installation documentation may
provide this as well as other vital
information.
2
Make sure the main transformer has been
correctly connected for the mains voltage level
at hand.
How to connect the transformer is found
under
3
Make sure the mains overload protection, FR1
has not tripped. If it has, reset it.
For information, see ‘Unit Description,
IRC5P’, Power Module / Fuses and
Overload Protections.
4
Check that the other fuses in the power supply
system are OK.
For information, see ‘Unit Description,
IRC5P’, Power Module / Fuses and
Overload Protections.
5
If the system does not start although the
controller seems to be working, make sure all
connections have been made correctly
between the modules.
Summary of Contents for IRC5P
Page 1: ...The heart of Robotics Product Manual Control Cabinet IRC5P 3HNA009834 001 en Rev 06 ...
Page 2: ......
Page 10: ...10 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Page 14: ...2 Safety 14 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Page 218: ...218 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P Manual Status ...