7 Repair
Product Manual, Control Cabinet IRC5P
149
7.11 Replacement of Fieldbus Adapter
7.11 Replacement of Fieldbus Adapter
Location
The EtherNet/IP or Profibus fieldbus adapter, if used, is located in the compact flash
slot inside the computer unit as shown below.
Figure 76 Computer unit, location of fieldbus adapter
References
–
’Replacement of Computer Unit’
Tools and Items
– Hand tools
Removal
The procedure describes how to remove a fieldbus adapter.
WARNING!
No repair work must be performed on the robot before the safety
on page 13 have been read and understood.
CAUTION!
The unit is sensitive to ESD. Before handling the unit, please observe
the safety information in
1.
Turn the electrical disconnect switch ‘off’ and lock switch in ‘off’ position.
WARNING!
Make sure that the mains switch is ‘off’ and locked in ‘off’ position
before continuing. Also make sure that possible other connected systems are ‘off’.
1.
Remove the Computer Unit assembly as described in procedure
2.
Remove cover attachment screws, disconnect fan unit connector and remove
cover.
1
Fieldbus adapter
2
Attachment screws fieldbus adapter
1
2