Control Modes 9-1
MN448
Chapter 9
Control Modes
The mode of operation can be easily selected by changing a couple of parameters. While starting up the drive, the user
selects the operating mode best suited for their purpose with parameters 9902 DIGITAL INPUTS FUNCTION SELECT and
1103 PRIMARY COMMAND SOURCE MODE.
9.1 Configuration Options
Common operating modes for Terminal Mode 1103 = 0 and Keypad Mode 1103 = 1 or 2 are in this section.
1103
Control Mode
Selected Speed Reference
0
Terminal Mode
Analog input 1
1
Keypad Mode (Unipolar)
Digital Potentiometer
2
Keypad Mode (Bipolar)
Digital Potentiometer
3
Modbus Network Control with Internal Accel/Decel Ramps
Speed reference via Fieldbus
4
Modbus Network Control with Internal Accel/Decel Ramps
Speed reference via Fieldbus
5
User PI mode
PI controller output
6
User PI Mode with Analog Input 1 Summation
PI controller output
9.2 Terminal Mode (
1103 = 0
), Parameter 9902 Settings
9902 Digital input 1
Digital Input 2
Digital Input 3 (An in 2)
Digital input 4 (An in 1)
Comments
0
Open: Stop
(disable)
Closed: Run
(enable)
Open: Forward run
Closed: Reverse run
Open: Analog input 1
Closed: Preset speed 1
Analog input 1
Factory Default 9902 = 0
1
Open: Stop
(disable)
Closed: Run
(enable)
Open: Analog input 1
Closed: Preset speed 1 / 2
Open: Preset speed 1
Closed: Preset speed 2
Analog input 1
2
Open: Stop
(disable)
Closed: Run
(enable)
Preset speed select 0
Preset speed select 1
Open: Preset speed 1...4
Closed: Max Speed
(
2008
)
3
1
Open: Stop
(disable)
Closed: Run
(enable)
Open: Analog input 1
Closed: Preset speed 1
External trip/thermistor input:
Open: Trip, Closed: Run
Analog input 1
Connect external
thermistor type PT100 or
similar to digital input 3
4
Open: Stop
(disable)
Closed: Run
(enable)
Open: Analog input 1
Closed: Analog input 2
Analog input 2
Analog input 1
Switches between selected
speed ref and Analog
input 2
5
Open: Fwd. Stop
Closed: Fwd. Run
Open: Reverse stop
Closed: Reverse run
Open: Analog input 1
Closed: Preset speed 1
Analog input 1
Closing digital inputs 1 and
2 together carries out a
fast stop
6
1
Open: Stop
(disable)
Closed: Run
(enable)
Open: Forward run
Closed: reverse run
External trip/thermistor input:
Open: Trip, Closed: Run
Analog input 1
Connect ext. thermistor
type PT100 or similar to
Digi input 3
7
1
Open: Fwd. Stop
Closed: Fwd. Run
Open: reverse stop
Closed: reverse run
External trip/thermistor input:
Open: Trip, Closed: Run
Analog input 1
Closing digital inputs 1 and
2 together carries out a
fast stop
8
Open: Stop
(disable)
Closed: Run
(enable)
Open: Forward run
Closed: Reverse run
Preset speed select 0
Preset speed select 1
Summary of Contents for EC Titanium ECS100A1H1DF4
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......