Parameter Definitions 10-5
MN448
Parameters in the Long parameter mode
No.
Name/Value
Description
Default
0000
READ ONLY PARAMETERS
Continued
Fault history
(read-only)
0190
DRIVE INTERNAL COOLING
FAN TOTAL OPERATING TIME
Displays the total operating time of the drive’s internal cooling fans.
The first value shown is the number of hours. Pressing the Up key
will display the minutes and seconds. This is used for scheduled
maintenance information (HH:MM:SS)
0192
DC BUS VOLTAGE RIPPLE
LOG (22ms) (V DC)
8 most recent values prior to trip, updated every 22ms.
0193
HEATSINK TEMPERATURE
LOG (30s) (°C)
8 most recent values prior to trip, updated every 30s.
0194
AMBIENT TEMPERATURE
LOG (30s) (°C)
8 most recent values prior to trip, updated every 30s.
0402
RUN TIME SINCE LAST TRIP
(1)
Run-time clock stopped by drive disable (or trip), reset on next enable only
if a trip occurred. Reset also on next enable after a drive power down. (0 to
99 999 hours)
0406
DC BUS VOLTAGE LOG
8 most recent values prior to trip, updated every 250ms. (0 … 1000V)
0415
RUN TIME SINCE LAST TRIP
(2)
Run-time clock stopped by drive disable (or trip), reset on next enable only
if a trip occurred (under-volts not considered a trip) – not reset by power
down / power up cycling unless a trip occurred prior to power down. (0 to
99 999 hours)
0416
RUN TIME SINCE LAST
DISABLE
Run-time clock stopped on drive disable, value reset on next enable. (0 to
99 999 hours)
0417
DRIVE EFFECTIVE
SWITCHING FREQUENCY
Actual drive effective output switching frequency. This value maybe lower
than the selected frequency in parameter 2606 EFFECTIVE SWITCHING
FREQUENCY if the drive is too hot. The drive will automatically reduce
the switching frequency to prevent an over temperature trip and maintain
operation. (4 to 32 kHz)
3301
SOFTWARE ID, IO & MOTOR
CTRL
e.g. “1.00”, “47AE”
Version number and checksum.
“1” on LH side indicates I/O processor,
“2“indicates motor control
3303
DRIVE SERIAL NUMBER
000000 … 999999
00-000 … 99-999
Unique drive serial number e.g. 540102 / 32 / 005
3304
DRIVE IDENTIFIER
04
FAULT HISTORY
Fault history (read-only)
0401
TRIP HISTORY LOG
When a fault is detected, it is stored in the fault history. Parameters 0401
Trip History Log can be used to display the last four fault codes for the
drive. Press Enter on the Remote Keypad to display the most recent fault.
Use the Up Down arrows to scroll through faults, the most recent fault is
displayed first.
Parameters 0402…0417 show drive operation data at the time of the latest
fault and run time since last trip.
See Chapter 13 Troubleshooting for a complete list of fault codes and
corrective actions.
-
Summary of Contents for EC Titanium ECS100A1H1DF4
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......