Parameter Definitions 10-9
MN448
Parameters in the Long parameter mode
No.
Name/Value
Description
Default
14
RELAY OUTPUTS
Status information indicated through relay output and relay operating
delays
1401
OUTPUT RELAY FUNCTION
SELECT
Selects the function assigned to the relay output. The relay has two output
terminals, Logic 1 indicates the relay is active, and therefore terminals 10
and 11 will be linked together.
1: Drive
READY
0:
DRIVE ENABLED
(RUNNING)
Logic 1 when the motor is enabled
1:
DRIVE READY
Logic 1 when power is applied to the drive and no fault exists
2:
AT TARGET FREQUENCY
(SPEED)
Logic 1 when the output frequency matches the setpoint frequency
3:
DRIVE TRIPPED
Logic 1 when the drive is in a fault condition
4:
OUTPUT FREQUENCY
>= LIMIT
Logic 1 when the output frequency exceeds the adjustable limit set in 3200
RELAY THRESHOLD LEVEL
5:
OUTPUT CURRENT >=
LIMIT
Logic 1 when the motor current exceeds the adjustable limit set in 3200
RELAY THRESHOLD LEVEL
6:
OUTPUT FREQUENCY
< LIMIT
Logic 1 when the output frequency is below the adjustable limit set in 3200
RELAY THRESHOLD LEVEL
7:
OUTPUT CURRENT <
LIMIT
Logic 1 when the motor current is below the adjustable limit set in 3200
RELAY THRESHOLD LEVEL
8:
ANALOG INPUT 2 >
LIMIT
Logic 1 when the signal on analog input 2 exceeds the adjustable limit set
in 3200 RELAY THRESHOLD LEVEL
9:
DRIVE READY TO RUN
Logic 1 when power is applied and the drive is enabled.
10: PULSE OUTPUT TO
INDICATE DRIVE HAS
TRIPPED
The pulsed output timing is to be as per the following diagram:
Trip pulse group for “Overvoltage/
Undervoltage” shown here, so 3
blinks/pulses
Trip pulse group is repeated after
every 15 sec’s until the trip is reset
15 sec’s
1 sec
1 sec
1 sec
1 sec
The number of pulses for a given trip are as follows:
Blinks/Pulses
Customer description of trip
Trip Code
Notes
3
Overvoltage
000
Drive internal DC bus high.
Under voltage
0006
Drive internal DC bus Low.
4
Motor Over temperature
_Ptc or 0009
PTC thermistor connected to drive indicates motor
is over temperature or drives internal motor thermal
overload shows motor is over temperature
Drive Over temperature
0003 or
O-Heat
Drive heatsink or drive internal temp too high.
5
Overcurrent
000
Output over current
6
Ext Fault (fault connected to a Digital input)
004
External trip as requested on digital input 3
7
Short Circuit
h O-I
Output short circuit
Constant on
Other trip
Any other trip not detailed within this table.
Summary of Contents for EC Titanium ECS100A1H1DF4
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......