10-10 Parameter Definitions
MN448
Parameters in the Long parameter mode
No.
Name/Value
Description
Default
15
ANALOG/DIGITAL OUTPUTS
Analog output signal processing
1501
ANALOG OUTPUT
FUNCTION SELECT
Selects the type of output signal information indicated from terminal 8.
Note:
When using settings 0 - 7 the output is a digital format (Logic 1 =
24V). When using settings 8-10 the output is an analog format.
8
0:
DRIVE ENABLED
(RUNNING)
Logic 1 when the
DRIVE
is enabled (Running)
1:
DRIVE READY
Logic 1 When no Fault condition exists on the drive
2:
AT TARGET
FREQUENCY (SPEED)
Logic 1 when the output frequency matches the set-point frequency
3:
DRIVE TRIPPED
Logic 1 when the drive is in a fault condition
4:
OUTPUT FREQUENCY
>= LIMIT
Logic 1 when the output frequency exceeds the adjustable limit set in
parameter
3200
RELAY THRESHOLD LEVEL
5:
OUTPUT CURRENT >=
LIMIT
Logic 1 when the motor current exceeds the adjustable limit set in
parameter
3200
RELAY THRESHOLD LEVEL
6:
OUTPUT FREQUENCY
< LIMIT
Logic 1 when the output frequency is below the adjustable limit set in
parameter
3200
RELAY THRESHOLD LEVEL
7:
OUTPUT CURRENT <
LIMIT
Logic 1 when the motor current is below the adjustable limit set in
parameter
3200
RELAY THRESHOLD LEVEL
8:
OUTPUT FREQUENCY
(MOTOR SPEED)
0 to parameter
2008 MAXIMUM FREQUENCY / SPEED LIMIT
9:
OUTPUT (MOTOR)
CURRENT
0 to 200% of parameter 9906 MOTOR RATED CURRENT
10: MOTOR POWER
0 to 200% of drive rated power.
16
SYSTEM CONTROLS
Parameter lock etc.
1602
PARAMETER ACCESS
UNLOCK
If Parameter
1603
has had a value entered, then the matching value needs
to be entered here in order to give read-write access to the parameters.
Refer to section 10.4 for detailed operation.
0
0…65535
1603
PARAMETER ACCESS CODE
DEFINITION
To make all parameters Read only, enter a value in this parameter. Refer to
section 10.4 for detailed operation.
0
0…65535
20
LIMITS
Drive operation limits
2007
MINIMUM FREQUENCY /
SPEED LIMIT
Minimum output frequency or motor speed limit – Hz or rpm.
If
9908
MOTOR RATED SPEED >0, the value entered / displayed is in RPM
0.0 Hz
0.0 HZ…
2008
Minimum frequency
2008
MAXIMUM FREQUENCY /
SPEED LIMIT
Maximum output frequency or motor speed limit – Hz or rpm.
If
9908
MOTOR RATED SPEED >0, the value entered / displayed is in RPM
133.0 Hz
2007…500.0 Hz
Maximum frequency
2020
BRAKE CHOPPER ENABLE
0
0:
MOTOR POWER
1:
ENABLED WITH
SOFTWARE
PROTECTION
Enables the internal brake chopper with software protection for a 200W
continuous rated resistor
2:
ENABLED WITHOUT
SOFTWARE
PROTECTION
Enables the internal brake chopper without software protection. An external
thermal protection device should be fitted.
3:
ENABLED WITH
SOFTWARE
PROTECTION
As setting 1, however the Brake chopper is only enabled during a change
of the frequency set-point and is disabled during constant speed operation.
4:
ENABLED WITHOUT
SOFTWARE
PROTECTION
As setting 2, however the Brake chopper is only enabled during a change
of the frequency set-point and is disabled during constant speed operation.
Summary of Contents for EC Titanium ECS100A1H1DF4
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......