2-2 General Information and Ratings
MN448
2.2 Nameplate and Type Designation Label
2.2.1 Motor Nameplate
The EC Titanium Motor nameplate is located on the side of the motor and includes NEMA rating, appropriate markings,
a type designation and a serial number, which allow identification of each unit. The motor nameplate contains electrical
information necessary for proper setup of a drive control, reference Figure 2.2 and Table 2-1 for detail.
Figure 2-2 Motor Nameplate Field Description
SYNCHRONOUS RELUCTANCE MOTOR
FOR INVERTER USE ONLY
READ INSTRUCTIONS BEFORE INSTALLING.
PERMANENT MAGNET MOTOR. WHEN SHAFT IS
ROTATED, VOLTAGE WILL BE GENERATED AT
THE MOTOR TERMINALS.
LIRE LES INSTRUCTIONS AVANT L’INSTALLATION,
MOTEUR Á AIMANT PERMANENT. LORSQUE
L'ARBRE TOURNE, UNE TENSION SERA GÉNÉRÉE
AUX BORNES DU MOTEUR.
BALDOR- RELIANCE
ELECTRONICALLY PROTECTED MOTOR
FOR INDUSTRIAL USE
SHAFT GROUNDING BRUSH INSTALLED
NP3968A01C01
ABB MOTOR AND MECHANICAL INC., FORT SMITH, AR. MFG. IN U.S.A.
WARNING/AVERTISSEMENT
EC-Titanium
TM
BEARING
RATING
VOLTS
R.P.M.
SPEC.
ENCL.
CAT. NO.
CT
TO
HZ
FRAME
Ld (mH)
IP
DE
ODE
VPWM
TO
CHP
HZ
VT
MATCHED INV
FLA
RPM MAX
PH.
CLASS
HZ
BEMF VOLTS
SER.F.
NEMA NOM. EFF
INV TYP
Lq (mH)
SER#
TO
HZ
PF
Rs OHM
HP
35E5247Z715G1
-
2
145T
TEFC
54
460
2.2
1800
60
1.0
4000
3
F
12.95
246
91.4%
40C AMB - CONT
109.6
505.5
60
6
1
ECI14A2P2
6205
6205
133
60
60
EN/IEC60034-1;-5
LISTED
E46145
1
ECS100A4H2140FF4
2
3
5
6
9
10
8
11
7
ECI4A2P2
4
12
14
13
FERRITE ASSISTED
Region Description
1
Catalog Number, see Figure 2.1 Type
designation key for details
2
General Motor Information (Frame,
Enclosure, IP Rating, Voltage, RPM, etc.)
3
Motor Rated Amps
4
BEMF (Back EMF) Voltage
5
Motor Stator Resistance (Rs)
6
Ld (mH) Motor Inductance (Lsd)
7
Lq (mH) Motor q-axis Inductance (Lsq)
8
Motor Rated Frequency
9
Matched Inverter Model Number
10
PM Motor Warning Information
11
Shaft Ground Provision Marking
12
QR Code for motor information
13
CE Marking
14
UL Agency Listing
2.2.2 Motor Setup Parameters
The following motor values shown on the nameplate and utilized for proper control and setup of a drive used to run the EC
Titanium motor. Parameter Numbers listed are for use with the Integrated Motor and Drive packages.
Table 2-1 Motor Setup Parameter Listing
Region
Description
Parameter
Number
3
Motor Rated Amps
9906
4
BEMF (Back EMF) Voltage
9905
5
Motor Stator Resistance (Rs)
11201
6
Ld (mH) Motor Inductance (Lsd)
11203
7
Lq (mH) Motor q-axis Inductance (Lsq)
11206
8
Motor Rated Frequency
9907
Motor Maximum Frequency
2008
Note:
Integrated motor and drive units have been factory programmed and parameters in Table 2-1 do not need to be
adjusted unless a software reset has been implemented.
Summary of Contents for EC Titanium ECS100A1H1DF4
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......