A new device name
mS3 6Byte In/Out PROFIsafe V2.6.1
is displayed under
the scanner in the
Configuration
tab page.
7 Click the new device name and check the settings in the
Properties
tab page
on the right pane of the window.
Make sure the Destination value is the same as the F-Destination address
value for the scanner in the
Safety Designer
software.
8 In the
I/O Engineering
tab, click
Cross Connections
in the
Configuration
group, and check the created signals.
Make sure the created signals are in the same name as the displayed signals.
9 In the
I/O Engineering
tab, click
Write Config
to write the configurations to
the controller.
10 Restart the controller.
11 After the controller is restarted, check the laser scanner name in RAPID
program InternalSpeedHandling_User in task T_ROB1, and make sure it is
consistent with the name that the user defines for the laser scanner.
If the names are inconsistent, use the following steps to modify:
a In the
Controller
pane, double-click the RAPID program
InternalSpeedHandling_User in task T_ROB1.
The RAPID program is displayed in the right pane.
b Find the parameter
Scanner1
and modify its value to the user-defined
laser scanner name.
Continues on next page
138
Product manual - CRB 1300
3HAC083111-001 Revision: B
© Copyright 2022-2023 ABB. All rights reserved.
3 Installation and commissioning
3.7.5.3 Configuration of one PROFIsafe-based laser scanner (RobotWare 7.10 or later and OmniCore
acting as Master)
Continued
Summary of Contents for CRB 1300
Page 1: ...ROBOTICS Product manual CRB 1300 ...
Page 50: ...This page is intentionally left blank ...
Page 662: ...This page is intentionally left blank ...
Page 690: ...This page is intentionally left blank ...
Page 704: ...This page is intentionally left blank ...
Page 720: ...This page is intentionally left blank ...
Page 725: ......