Operation principle
1.
The Safe torque off activates (the activation switch is opened, or safety relay contacts
open).
2.
The STO inputs of the drive control unit de-energize.
3.
The control unit cuts off the control voltage from the output IGBTs.
4.
The control program generates an indication as defined by parameter
31.22
(refer to
the firmware manual of the drive).
The parameter selects which indications are given when one or both STO signals are
switched off or lost. The indications also depend on whether the drive is running or
stopped when this occurs.
Note:
This parameter does not affect the operation of the STO function itself. The STO function
will operate regardless of the setting of this parameter: a running drive will stop upon
removal of one or both STO signals, and will not start until both STO signals are restored
and all faults reset.
Note:
The loss of only one STO signal always generates a fault as it is interpreted as a
malfunction of STO hardware or wiring.
5.
The motor coasts to a stop (if running). The drive cannot restart while the activation
switch or safety relay contacts are open. After the contacts close, a reset may be needed
(depending on the setting of parameter
31.22
). A new start command is required to start
the drive.
190 The Safe torque off function
Summary of Contents for ACS880-37LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 78: ...78 ...
Page 116: ...116 ...
Page 134: ...5 Set the real time clock 134 Maintenance ...
Page 144: ...144 ...
Page 167: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 167 ...
Page 169: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 169 ...
Page 170: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 170 Dimensions ...
Page 172: ...Location and size of input terminals Contact ABB for details 172 Dimensions ...
Page 174: ...Inverter module cubicle with two R8i modules bottom cable exit 174 Dimensions ...
Page 175: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 175 ...
Page 176: ...Brake chopper cubicle D150 176 Dimensions ...
Page 178: ...Cubicle width 300 mm top cable exit 178 Dimensions ...
Page 179: ...Cubicle width 400 mm bottom cable exit Dimensions 179 ...
Page 180: ...Cubicle width 400 mm top cable exit 180 Dimensions ...
Page 181: ...Cubicle width 600 mm bottom cable exit Dimensions 181 ...
Page 182: ...Cubicle width 600 mm top cable exit 182 Dimensions ...
Page 198: ...198 ...
Page 200: ...200 ...