or ground them indirectly via a high-frequency capacitor with a few nanofarads, for example
3.3 nF / 630 V. The shield can also be grounded directly at both ends if they are in the same
ground line with no significant voltage drop between the end points.
XAI
XAO
AIn+
AIn-
AOn
AGND
1)
2)
T
T
T
1
…
3 × Pt100/Pt1000/PTC or 1 × KTY84
1)
Set the input type to voltage with the appropriate switch or jumper on the inverter control
unit. Make the corresponding setting in the inverter unit control program in parameter group
12 Standard AI
.
2)
Select the excitation mode in parameter group
13 Standard AO
of inverter unit control
program.
WARNING!
As the inputs pictured above are not insulated according to IEC/EN 60664, the
connection of the motor temperature sensor requires double or reinforced insulation
between motor live parts and the sensor. If the assembly does not fulfill the
requirement, the I/O board terminals must be protected against contact and must
not be connected to other equipment or the temperature sensor must be isolated
from the I/O terminals.
DIIL input
The DIIL input is used for the connection of safety circuits. The input is parametrized to stop
the unit when the input signal is lost.
Note:
This input is NOT SIL or Pl certified.
The XD2D connector
The XD2D connector provides an RS-485 connection that can be used for
•
basic master/follower communication with one master drive and multiple followers,
•
fieldbus control through the embedded fieldbus interface (EFB), or
•
drive-to-drive (D2D) communication implemented by application programming.
See the firmware manual of the drive for the related parameter settings.
Enable bus termination on the units at the ends of the drive-to-drive link. Disable bus
termination on the intermediate units.
106 Control units of the drive
Summary of Contents for ACS880-37LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 78: ...78 ...
Page 116: ...116 ...
Page 134: ...5 Set the real time clock 134 Maintenance ...
Page 144: ...144 ...
Page 167: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 167 ...
Page 169: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 169 ...
Page 170: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 170 Dimensions ...
Page 172: ...Location and size of input terminals Contact ABB for details 172 Dimensions ...
Page 174: ...Inverter module cubicle with two R8i modules bottom cable exit 174 Dimensions ...
Page 175: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 175 ...
Page 176: ...Brake chopper cubicle D150 176 Dimensions ...
Page 178: ...Cubicle width 300 mm top cable exit 178 Dimensions ...
Page 179: ...Cubicle width 400 mm bottom cable exit Dimensions 179 ...
Page 180: ...Cubicle width 400 mm top cable exit 180 Dimensions ...
Page 181: ...Cubicle width 600 mm bottom cable exit Dimensions 181 ...
Page 182: ...Cubicle width 600 mm top cable exit 182 Dimensions ...
Page 198: ...198 ...
Page 200: ...200 ...