Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Transportation
in the protective package
Storage
in the protective package
Operation
installed for stationary
use
-
-
0…2000 m (0…6562 ft)
above sea level. For alti-
tudes over 2000 m, contact
ABB.
Installation site altitude
Output derated above 1000
m (3281 ft).
-40 to +70 °C (-
40 to +158 °F)
-40 to +70 °C (-
40 to +158 °F)
0 … +45 °C
(+32 … +113 °F), no con-
densation allowed. Output
derated in the range
+45 … +55 °C
(+113 … +131 °F).
Air temperature
Max. 95%
Max. 95%
Max. 95%
Relative humidity
No condensation allowed. Maximum allowed relative humidity is 60% in the presence
of corrosive gases.
IEC 60721-3-2:1997
IEC 60721-3-1:1997
IEC/EN 60721-3-3:2002:
Classification of environ-
mental conditions - Part 3-
3: Classification of groups
of environmental paramet-
ers and their severities -
Stationary use of weather
protected locations
Contamination
Chemical gases: Class
2C2
Solid particles: Class 2S2
Chemical gases: Class
1C2
Solid particles: Class 1S3
(packing must support this,
otherwise 1S2)
Chemical gases: Class
3C2
Solid particles: Class 3S2.
No conductive dust al-
lowed.
IEC/EN 60721-3-2:1997
IEC/EN 60721-3-1:1997
IEC/EN 60721-3-3:2002
Vibration
2…9 Hz: max. 3.5 mm
amplitude
10…57 Hz: max. 0.075 mm
amplitude
10…57 Hz: max. 0.075 mm
amplitude
IEC/EN 61800-5-1
IEC 60068-2-6:2007,
EN 60068-2-6:2008 Envir-
onmental testing Part 2:
Tests –Test Fc: Vibration
(sinusoidal)
9…200 Hz: 10 m/s
2
(32.8 ft/s
2
)
57…150 Hz: 1
g
57…150 Hz: 1
g
Units with marine construc-
tion (C121): Max.
1 mm (0.04 in)
(5 … 13.2 Hz), max. 0.7
g
(13.2 … 100 Hz) sinusoidal
With packing max.
100 m/s
2
(328 ft/s
2
) 11 ms
With packing max.
100 m/s
2
(328 ft/s
2
) 11 ms
Not allowed
Shock
IEC 60068-2-27:2008, EN
60068-2-27:2009
Environmental testing -
Part 2-27: Tests - Test Ea
and guidance: Shock
Technical data 157
Summary of Contents for ACS880-37LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 78: ...78 ...
Page 116: ...116 ...
Page 134: ...5 Set the real time clock 134 Maintenance ...
Page 144: ...144 ...
Page 167: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 167 ...
Page 169: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 169 ...
Page 170: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 170 Dimensions ...
Page 172: ...Location and size of input terminals Contact ABB for details 172 Dimensions ...
Page 174: ...Inverter module cubicle with two R8i modules bottom cable exit 174 Dimensions ...
Page 175: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 175 ...
Page 176: ...Brake chopper cubicle D150 176 Dimensions ...
Page 178: ...Cubicle width 300 mm top cable exit 178 Dimensions ...
Page 179: ...Cubicle width 400 mm bottom cable exit Dimensions 179 ...
Page 180: ...Cubicle width 400 mm top cable exit 180 Dimensions ...
Page 181: ...Cubicle width 600 mm bottom cable exit Dimensions 181 ...
Page 182: ...Cubicle width 600 mm top cable exit 182 Dimensions ...
Page 198: ...198 ...
Page 200: ...200 ...