Operation principle and hardware description 23
3
Operation principle and
hardware description
What this chapter contains
This chapter describes the operation principle and construction of the wind turbine
converter.
Operation principle
ACS800-67LC liquid-cooled wind turbine converter is used with induction generators with
wound rotor and slip rings, such as the ABB AMK series. The converter is connected
between the generator rotor and the power supply network. The converter can be installed
in a downtower cabinet, tower or in the nacelle.
Doubly-fed asynchronous generators are essentially wound rotor induction generators
with variable frequency excitation of the rotor circuit, incorporating rotor direct torque
control (DTC) via power converter. The rotor control is four-quadrant, allowing
independent control of real and reactive power flow in either direction (rotor to grid or grid
to rotor), or confined to unidirectional (grid to rotor) active power flow.
Induction generators have a gearbox for coupling the generator shaft to turbine hub, active
control of turbine blade pitch for maximizing production and controlling mechanical speed,
and variable speed operation depending on the rating of power converter relative to
turbine rating (typically ±30% of the generator synchronous speed).
In doubly-fed systems the stator circuit of the generator is connected to the power supply
network (grid) while the rotor circuit is connected to a converter via slip rings. In a doubly-
fed concept the size of the power converter is significantly smaller than in eg, full-power
concept because only one-third of the rated generator power is fed through the converter
Summary of Contents for ACS800-67LC
Page 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 52: ...52 Mechanical installation ...
Page 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Page 92: ...92 Maintenance 4 6 5 5 ...
Page 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Page 109: ...Maintenance 109 5 6 7 ...
Page 131: ...Technical data 131 Declaration of incorporation ...
Page 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Page 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Page 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Page 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Page 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Page 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Page 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Page 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Page 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Page 147: ...Dimension drawings 147 Option 2H372 ...
Page 148: ...148 Dimension drawings Option 3H372 ...
Page 149: ...Dimension drawings 149 Option 1H373 ...
Page 150: ...150 Dimension drawings Option 2H373 ...
Page 151: ...Dimension drawings 151 Option 3H373 ...