12 Safety instructions
Hot surface warning
warns about hot surfaces. Some parts inside the converter
cabinet remain hot for a while after the disconnection of input power.
Safety in installation and
maintenance
Electrical safety
These warnings are intended for all who work on the converter or generator. Ignoring the
instructions can cause physical injury or death, or damage to the equipment.
WARNING!
•
Only qualified electricians are allowed to install and maintain the converter!
•
Before working in the incoming cubicle, isolate the whole converter from the electrical
power supply network. The load switch disconnector (C111) or air circuit
breaker (oC108/+109) does not remove the voltage from the grid-side
connection terminals of the converter.
•
Never work on the converter or generator when input power is applied. After
disconnecting the input power, always wait for 10 minutes to let the intermediate circuit
capacitors discharge before you start working on the converter or generator. Always
ensure by measuring with a multimeter the voltage between the power terminals and
earth and DC link and earth that the converter does not have any live parts before
beginning work.
•
Apply temporary grounding before working on the unit. The converter does not have
internal grounding device, therefore external equipment is required.
•
Do not work on the control cables when input power is applied to the converter or to
the external control circuits. Externally supplied control circuits (eg, UPS) may carry
dangerous voltage even when the input power of the converter is switched off.
•
Live parts inside the cubicle are protected against direct contact. However, pay special
attention when handling metallic shrouds. The cabinet is protected to IP54 only when
doors are closed.
•
Do not make any withstand voltage tests on the converter.
•
Isolate the cables from the converter when testing the insulation resistance or
withstand voltage of the power cables or the generator.
•
When reconnecting the cables, always check that the phase order is correct.
Note:
•
The rotor cable terminals may contain a dangerously high voltage when the input
power is on, regardless of whether the generator is running or not.
•
The converter DC link may contain a dangerously high voltage, regardless of whether
the converter is running or not.
•
Depending on the external wiring, dangerous voltage (115 V or 230 V) may be present
on the relay outputs of the converter system.
Summary of Contents for ACS800-67LC
Page 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 52: ...52 Mechanical installation ...
Page 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Page 92: ...92 Maintenance 4 6 5 5 ...
Page 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Page 109: ...Maintenance 109 5 6 7 ...
Page 131: ...Technical data 131 Declaration of incorporation ...
Page 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Page 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Page 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Page 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Page 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Page 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Page 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Page 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Page 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Page 147: ...Dimension drawings 147 Option 2H372 ...
Page 148: ...148 Dimension drawings Option 3H372 ...
Page 149: ...Dimension drawings 149 Option 1H373 ...
Page 150: ...150 Dimension drawings Option 2H373 ...
Page 151: ...Dimension drawings 151 Option 3H373 ...