Electrical installation 71
Connection procedure – sealing modules at the cable lead-through
For description of the sealing modules, see chapter
Operation principle and hardware
, page
. Sealing modules are to be installed by the customer and they are
located unfastened in the cubicles they are to be installed in.
WARNING!
Read and follow the instructions given in chapter
.
Ignoring the instructions can cause physical injury or death, or damage to the
equipment.
1. Open the door of the incoming cubicle. Unlock the handle, release it from the holder
and turn upwards to release the door locking mechanism.
2. Remove the shroud that protects the cable connection busbars and cable entries.
3. Remove the blank plate and the gasket under it.
4. Follow the instructions below.
Fasten the gasket to the collar plate
(a).
Fasten the sealing module frame to
the collar plate (b).
Fasten both parts onto the cabinet
(c).
Lubricate the inside of all
frame openings
thoroughly with lubricant.
Put some extra lubricant
in all corners of all frame
openings.
Route all cables. It is
recommended to seal
cables at the bottom of
the frame and put spare
modules on top.
a
b
c
Summary of Contents for ACS800-67LC
Page 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 52: ...52 Mechanical installation ...
Page 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Page 92: ...92 Maintenance 4 6 5 5 ...
Page 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Page 109: ...Maintenance 109 5 6 7 ...
Page 131: ...Technical data 131 Declaration of incorporation ...
Page 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Page 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Page 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Page 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Page 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Page 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Page 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Page 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Page 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Page 147: ...Dimension drawings 147 Option 2H372 ...
Page 148: ...148 Dimension drawings Option 3H372 ...
Page 149: ...Dimension drawings 149 Option 1H373 ...
Page 150: ...150 Dimension drawings Option 2H373 ...
Page 151: ...Dimension drawings 151 Option 3H373 ...