118 The internal cooling circuit
Maximum coolant inlet temperature for the converter
Maximum inlet temperature variation:
±4°C
Maximum temperature rise:
13°C; depends on mass flow.
Pressure limits
Base pressure:
100…150 kPa (recommended); 200 kPa (maximum). “Base pressure”
denotes the pressure of the system compared with the atmospheric pressure when the
cooling circuit is filled with coolant.
Maximum design pressure:
600 kPa (6 bar)
Nominal pressure difference:
130 kPa (1.3 bar) / 140 kPa (1.4 bar) (hydrostatic)
Maximum pressure difference:
170 kPa (1.7 bar) / 180 kPa (1.8 bar) (hydrostatic)
Working pressure:
min. 120 kPa (1.2 bar)
Pressure monitoring:
Pressure at the measuring point must stay within the range of
120 kPa...380 kPa (1.2…3.8 bar) for the converter to operate.
T
air
(°C)
Min.
T
coolant
(°C)
φ
= 95%
φ
= 80%
φ
= 65%
φ
= 50%
φ
= 40%
5
5.0
5.0
5.0
5.0
5.0
10
9.2
6.7
5.0
5.0
5.0
15
14.2
11.5
8.4
5.0
5.0
20
19.2
16.5
13.2
9.4
6.0
25
24.1
21.4
17.9
13.8
10.5
30
29.1
26.2
22.7
18.4
15.0
35
34.1
31.1
27.4
23.0
19.4
40
39.0
35.9
32.2
27.6
23.8
45
44.0
40.8
36.8
32.1
28.2
50
49.0
45.6
41.6
36.7
32.8
00553829
= Not allowed as standard but the coolant temperature must be 5 °C or
above. Consult an ABB representative if operation below coolant
temperature 5 °C is required.
Example:
At an air temperature of 45 °C and relative humidity of 65% the coolant
temperature may not be below +36.8 °C
Range
Converter output current derating
5 °C (41 °F)
minimum coolant inlet temperature
50 °C (122 °F)
maximum coolant inlet temperature with derating
Summary of Contents for ACS800-67LC
Page 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 52: ...52 Mechanical installation ...
Page 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Page 92: ...92 Maintenance 4 6 5 5 ...
Page 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Page 109: ...Maintenance 109 5 6 7 ...
Page 131: ...Technical data 131 Declaration of incorporation ...
Page 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Page 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Page 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Page 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Page 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Page 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Page 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Page 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Page 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Page 147: ...Dimension drawings 147 Option 2H372 ...
Page 148: ...148 Dimension drawings Option 3H372 ...
Page 149: ...Dimension drawings 149 Option 1H373 ...
Page 150: ...150 Dimension drawings Option 2H373 ...
Page 151: ...Dimension drawings 151 Option 3H373 ...