124 Technical data
Notes:
•
Larger fuses must not be used.
•
Use always the fuses that are specified by ABB.
•
The recommended fuses are for branch circuit protection per NEC as required for UL
approval.
•
Make sure that fuses within a converter are made by the same manufacturer.
Dimensions and free space requirements
400 mm free space is needed above to allow opening of pressure relief lids (that open automatically upon arc
fault). Lids need at least 200 mm space to open.
150 mm free space is needed at the right-hand side for the control cable plug-in connectors.
115 mm free space is needed at the right or left hand side of the converter for the cooling pipe connections
(depending on which side the cooling connections are).
Losses, cooling data and noise
1) With 200 mm or 400 mm (C111) wide incoming cubicle
2) With power cabinet (C108 or +C109)
3) With DC chopper (D150)
4) With 400 mm wide incoming cubicle (C111) and DC chopper (D150)
5) With power cabinet (C108 or +C109) and DC chopper (D150)
Type
Height (mm)
Depth (mm)
Width (mm)
ICU 200 mm
ICU 400 mm
(+C111)
ACS800-67LC-1075/0575-7
2000
644
1600
1800
ACS800-67LC-1375/0575-7
2000
644
1600
1800
ACS800-67LC-1375/1125-7
2000
644
1800
2000
ACS800-67LC-1595/0865-7
2000
644
2000
2200
ACS800-67LC-2035/1125-7
2000
644
2000
2200
ACS800-67LC-
Losses kW
Maximum
total losses
1), 3), 4)
Maximum
total losses
2), 5)
Maximum
P
loss tot coolant
1), 3), 4)
Maximum
P
loss tot coolant
2), 5)
Maximum
P
loss tot air
1), 3), 4)
Maximum
P
loss tot air
2), 5)
1075/0575-7
27
31
26
30
0.5
0.6
1375/0575-7
30
34
29
33
0.6
0.7
1375/1125-7
40
45
40
44
0.8
0.9
1595/0865-7
44
50
43
49
0.9
1.0
2035/1125-7
57
63
56
62
1.1
1.3
ACS800-67LC-
Pressure loss kPa (bar)
1), 2), 3), 4, 5)
Noise level dB
1), 2), 3), 4, 5)
All types
100 (1.0)
<70
Summary of Contents for ACS800-67LC
Page 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 52: ...52 Mechanical installation ...
Page 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Page 92: ...92 Maintenance 4 6 5 5 ...
Page 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Page 109: ...Maintenance 109 5 6 7 ...
Page 131: ...Technical data 131 Declaration of incorporation ...
Page 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Page 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Page 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Page 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Page 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Page 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Page 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Page 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Page 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Page 147: ...Dimension drawings 147 Option 2H372 ...
Page 148: ...148 Dimension drawings Option 3H372 ...
Page 149: ...Dimension drawings 149 Option 1H373 ...
Page 150: ...150 Dimension drawings Option 2H373 ...
Page 151: ...Dimension drawings 151 Option 3H373 ...