30 Operation principle and hardware description
Crowbar
The converter is equipped with active crowbar(s) as standard. The crowbar consists of
crowbar unit (type ACBU-Ax) and crowbar resistor (type ACBU-Rx).
The crowbar circuit is used for DC overvoltage protection in abnormal grid conditions, eg,
short interruptions or voltage dip/sag events. Active crowbar is needed when the converter
must stay connected to the grid during grid faults. The crowbar can be switched ON and
OFF by the rotor-side converter. This allows the converter to be connected to the grid even
during very severe grid faults.
Crowbar is triggered if the DC link voltage is too high or alternatively if the rotor current is
too high. Active crowbar is controlled by the rotor-side converter control program but in
case of internal failure it can protect the converter independently. Circuit diagram and
layout of the crowbar is shown below.
Crowbar (ACBU-Ax)
x
No.
Description
1
DC connections (UDC+ and UDC-)
2
Fiber optic connectors of the AITF
board (inside the cover). Connected to
the control units.
3
Terminal block (klixon)
4
Terminal block (triggered)
5
Crowbar resistor
6
AC connections (U2, V2, W2).
Connector for AC input connection is
located under the cover.
1
2
3
4
5
6
Summary of Contents for ACS800-67LC
Page 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 52: ...52 Mechanical installation ...
Page 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Page 92: ...92 Maintenance 4 6 5 5 ...
Page 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Page 109: ...Maintenance 109 5 6 7 ...
Page 131: ...Technical data 131 Declaration of incorporation ...
Page 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Page 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Page 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Page 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Page 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Page 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Page 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Page 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Page 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Page 147: ...Dimension drawings 147 Option 2H372 ...
Page 148: ...148 Dimension drawings Option 3H372 ...
Page 149: ...Dimension drawings 149 Option 1H373 ...
Page 150: ...150 Dimension drawings Option 2H373 ...
Page 151: ...Dimension drawings 151 Option 3H373 ...