The internal cooling circuit 119
Water quality
Freeze protection and corrosion inhibition
Depending on the ambient temperature, add antifreeze and corrosion inhibitor to the
coolant (see
below). If you use one of the following types of
antifreeze that contain both freeze protector and corrosion inhibitor, no additional corrosion
inhibitor is needed:
•
Clariant Antifrogen N
•
Clariant Antifrogen L
•
BASF Glysantin G30
•
DOW company Dowcal 20
If you use DOW industrial grade propylene glycol (PGI), add an amount of Cortec VpCI-
649 that makes up 0.5% of the total coolant quantity in the circuit.
Glycol concentration
The graph below shows the required glycol concentration in weight percentage according
to ambient/storage temperature
T
.
WARNING!
Operation at temperatures below 5 °C (41 °F) is not permitted even
with antifreeze.
Note:
If more than 25% is added, the pressure loss in the system increases. An operating
pressure of more than 150 kPa is required for sufficient flow.
Tap water
The use of tap water is allowed as follows. Tap water must fulfil the requirements of the Council Directive 98/
83/EC of 3/11/98 on the quality of water intended for human consumption. Corrosion inhibition with 0.5% by
volume Cortec VCI-649 is required.
pH value
6…9
Chloride
< 50 mg/l
Sulphate
< 100 mg/l
Total dissolved solids
< 200 mg/l, no deposits are allowed at the tempera-
ture of +57 °C
Total hardness as CaCO
3
< 250 mg/l
Conductivity
< 400 µS/cm (this equals the resistance of > 2500
ohm/cm)
The water must be clean of solid matter.
0
20
40
60
80
-50
-40
-30
-10
0
-20
T
(°C)
+5
Glycol concentration% (weight)
Summary of Contents for ACS800-67LC
Page 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 52: ...52 Mechanical installation ...
Page 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Page 92: ...92 Maintenance 4 6 5 5 ...
Page 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Page 109: ...Maintenance 109 5 6 7 ...
Page 131: ...Technical data 131 Declaration of incorporation ...
Page 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Page 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Page 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Page 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Page 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Page 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Page 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Page 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Page 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Page 147: ...Dimension drawings 147 Option 2H372 ...
Page 148: ...148 Dimension drawings Option 3H372 ...
Page 149: ...Dimension drawings 149 Option 1H373 ...
Page 150: ...150 Dimension drawings Option 2H373 ...
Page 151: ...Dimension drawings 151 Option 3H373 ...