Installation with 50mm space
between
Install side-by-side
Frame
0%
20%
40%
60%
80%
100%
-10
0
10 20 30 40 50 60 70
Derating
factor
90%
Ambient temperature
(°C)
(°F)
158
140
122
104
86
68
50
32
14
Derating factor for
IN, ILd and IHd on
ACS180-04x-
048A-2,
045A-4
R4
0%
20%
40%
60%
80%
100%
-10
0
10 20 30 40 50 60 70
Derating
factor
Ambient temperature
(°C)
(°F)
158
140
122
104
86
68
50
32
14
Derating factor for
IN, ILd and IHd on
ACS180-04x-
055A-2,
038A-4,
050A-4
■
Altitude derating
1000...2000 m above sea level, the derating is 1% for every 100 m (330 ft).
To calculate the output current, multiply the current in the rating table with the
derating factor k, which for x meters (1000 m <= x <= 2000 m) is:
■
Switching frequency derating
Current multiplier with different switching frequencies
Type
ACS180-04...
12 kHz
8 kHz
4 kHz
2 kHz
1-phase Un = 200 ... 240 V
0.7
0.8
1
1
-02A4-1
0.7
0.8
1
1
-03A7-1
0.7
0.8
1
1
-04A8-1
0.7
0.8
1
1
-06A9-1
0.7
0.8
1
1
-07A8-1
0.7
0.8
1
1
-09A8-1
0.7
0.8
1
1
-12A2-1
3-phase Un = 200 ... 240 V
0.7
0.8
1
1
-02A4-2
Technical data 99
Summary of Contents for ACS180
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 36: ...36...
Page 41: ...4 Tighten the mounting screws Mechanical installation 41...
Page 58: ...58...
Page 76: ...76...
Page 90: ...90...
Page 130: ...Frame R0 130 Dimension drawings...
Page 131: ...Frame R1 Dimension drawings 131...
Page 133: ...Frame R3 Dimension drawings 133...
Page 134: ...Frame R4 134 Dimension drawings...
Page 142: ...142...
Page 162: ...Declarations of conformity 162 The Safe torque off function...
Page 163: ...The Safe torque off function 163...
Page 164: ...164 The Safe torque off function...
Page 165: ...The Safe torque off function 165...
Page 166: ...166...