Additional information on the control connections
■
Connecting EIA-485 fieldbus cable to the drive
Connect the fieldbus to the EIA-485 Modbus RTU terminal on the front of the drive.
The EIA-485 network uses shielded, twisted-pair cable for data signaling with
characteristic impedance between 100 and 130 ohm. The distributed capacitance
between conductors is less than 100 pF per meter (30 pF per foot). Distributed
capacitance between conductors and shield is less than 200 pF per meter (60 pF
per foot). Foil or braided shields are acceptable. The connection diagram is shown
below.
With signal ground reference terminal
G
R
-
+
1
B+
A-
AGND
Shield
J1
J2
4
B+
A-
AGND
Shield
J1
J2
3
B+
A-
AGND
Shield
J1
J2
2
Without signal ground reference terminal
G
-
+
1
100 ohm
B+
A-
AGND
Shield
J1
J2
4
B+
A-
AGND
Shield
J1
J2
3
B+
A-
AGND
Shield
J1
J2
2
Fieldbus controller. Termination ON
1)
.
1
Drive. J1: Termination OFF; J2: Modbus Mode
2
Drive. J1: Termination OFF; J2: Modbus Mode
3
Drive at the end of the communication line. J1: Termination ON
; J2: Modbus
Mode
4
1) Note: The device at both ends on the fieldbus must have termination set to ON.
72 Electrical installation
Summary of Contents for ACS180
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 36: ...36...
Page 41: ...4 Tighten the mounting screws Mechanical installation 41...
Page 58: ...58...
Page 76: ...76...
Page 90: ...90...
Page 130: ...Frame R0 130 Dimension drawings...
Page 131: ...Frame R1 Dimension drawings 131...
Page 133: ...Frame R3 Dimension drawings 133...
Page 134: ...Frame R4 134 Dimension drawings...
Page 142: ...142...
Page 162: ...Declarations of conformity 162 The Safe torque off function...
Page 163: ...The Safe torque off function 163...
Page 164: ...164 The Safe torque off function...
Page 165: ...The Safe torque off function 165...
Page 166: ...166...