European Union and United Kingdom
To comply with European Union directives and United Kingdom regulations related
to standard EN 60204-1, the disconnecting device must be one of these types:
•
switch-disconnector of utilization category AC-23B (IEC 60947-3)
•
disconnector that has an auxiliary contact that in all cases causes switching
devices to break the load circuit before the opening of the main contacts of
the disconnector (EN 60947-3)
•
circuit-breaker suitable for isolation in accordance with IEC 60947-2.
■
North America
Installations must be compliant with NFPA 70 (NEC)
1)
and/or Canadian Electrical
Code (CE) along with state and local codes for your location and application.
1)
National Fire Protection Association 70 (National Electric Code).
■
Other regions
The disconnecting device must conform to the applicable local safety regulations.
Selecting the main contactor
You can equip the drive with a main contactor.
Follow these guidelines when you select a main contactor:
•
Dimension the contactor according to the nominal voltage and current of the
drive. Also consider the environmental conditions such as surrounding air
temperature.
•
Select contactor with utilization category AC-1 (number of operations under
load) according to IEC 60947-4,
Low-voltage switch gear and control gear.
•
Consider the application life time requirements.
Checking the compatibility of the motor and drive
Use asynchronous AC induction motor, or permanent magnet synchronous motor
with the drive. Multiple induction motors can be connected to the drive at a time
when using the scalar motor control mode.
Make sure that the motor(s) and the drive are compatible according to the rating
table in the technical data.
44 Guidelines for planning the electrical installation
Summary of Contents for ACS180
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 36: ...36...
Page 41: ...4 Tighten the mounting screws Mechanical installation 41...
Page 58: ...58...
Page 76: ...76...
Page 90: ...90...
Page 130: ...Frame R0 130 Dimension drawings...
Page 131: ...Frame R1 Dimension drawings 131...
Page 133: ...Frame R3 Dimension drawings 133...
Page 134: ...Frame R4 134 Dimension drawings...
Page 142: ...142...
Page 162: ...Declarations of conformity 162 The Safe torque off function...
Page 163: ...The Safe torque off function 163...
Page 164: ...164 The Safe torque off function...
Page 165: ...The Safe torque off function 165...
Page 166: ...166...