Do not do work on the drive when a rotating permanent magnet motor is
connected to it. A rotating permanent magnet motor energizes the drive
including its input and output power terminals.
Before installation, start-up and maintenance work on the drive:
•
Stop the drive.
•
Disconnect the motor from the drive with a safety switch or by other means.
•
If you cannot disconnect the motor, make sure that the motor cannot rotate
during work. Make sure that no other system, like hydraulic crawling drives,
can rotate the motor directly or through any mechanical connection like belt,
nip, rope, etc.
•
Do the steps in section
Electrical safety precautions (page 16)
•
Install temporary grounding to the drive output terminals (T1/U, T2/V, T3/W).
Connect the output terminals together as well as to the PE.
During the start-up:
•
Make sure that the motor cannot run overspeed, for example, driven by the
load. Motor overspeed causes overvoltage that can damage or destroy the
capacitors in the intermediate circuit of the drive.
■
Safety in operation
WARNING!
Make sure that the motor cannot run overspeed, for example, driven by the
load. Motor overspeed causes overvoltage that can damage or destroy the
capacitors in the intermediate circuit of the drive.
20 Safety instructions
3
Summary of Contents for ACS180
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 36: ...36...
Page 41: ...4 Tighten the mounting screws Mechanical installation 41...
Page 58: ...58...
Page 76: ...76...
Page 90: ...90...
Page 130: ...Frame R0 130 Dimension drawings...
Page 131: ...Frame R1 Dimension drawings 131...
Page 133: ...Frame R3 Dimension drawings 133...
Page 134: ...Frame R4 134 Dimension drawings...
Page 142: ...142...
Page 162: ...Declarations of conformity 162 The Safe torque off function...
Page 163: ...The Safe torque off function 163...
Page 164: ...164 The Safe torque off function...
Page 165: ...The Safe torque off function 165...
Page 166: ...166...