Separate control cable ducts
Put 24 V DC and 230 V AC (120 V AC) control cables in separate ducts, unless the
24 V DC cable is insulated for 230 V AC (120 V AC) or insulated with an insulation
sleeving for 230 V AC (120 V AC).
24 V DC
230 V AC
(120 V AC)
230 V AC
(120 V AC)
24 V DC
Implementing short-circuit and thermal overload protection
■
Protecting the drive and input power cable in short-circuits
Use the fuses specified for the drive in the technical data. Make sure that also the
electric power supply network meets the specification (minimum allowed
short-circuit current that the fuse selection is based on).
The fuses restrict drive damage and prevent damage to adjoining equipment in
case of a short-circuit inside the drive. When located at the distribution board, the
fuses also protect the input power cable against short circuits.
See the drive technical data for alternative short-circuit protections.
■
Protecting the motor and motor cable in short-circuits
The drive protects the motor cable and motor in a short-circuit situation when:
•
the motor cable is sized correctly
•
the motor cable type complies with the motor cable selection guidelines by
ABB
•
the cable length does not exceed the allowed maximum length specified for
the drive
•
the setting of parameter 99.10 Motor nominal power in the drive is equal with
the value given on the motor rating plate.
The electronic power output short-circuit protection circuitry meets the
requirements of IEC 60364-4-41 2005/AMD1.
Guidelines for planning the electrical installation 53
Summary of Contents for ACS180
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 36: ...36...
Page 41: ...4 Tighten the mounting screws Mechanical installation 41...
Page 58: ...58...
Page 76: ...76...
Page 90: ...90...
Page 130: ...Frame R0 130 Dimension drawings...
Page 131: ...Frame R1 Dimension drawings 131...
Page 133: ...Frame R3 Dimension drawings 133...
Page 134: ...Frame R4 134 Dimension drawings...
Page 142: ...142...
Page 162: ...Declarations of conformity 162 The Safe torque off function...
Page 163: ...The Safe torque off function 163...
Page 164: ...164 The Safe torque off function...
Page 165: ...The Safe torque off function 165...
Page 166: ...166...