Installation Manual
H3C S7500 Series Ethernet Switches
Appendix B N68 Cabinet Installation
B-52
(1) Cabinet
(2) Antistatic floor
Figure B-50
Cabinets installed on the raised antistatic floor
B.3.10 Verifying Installation
The following requirements must be satisfied:
z
The positions of the cabinets must comply with the construction design.
z
All the bolts used to fix support and cabinets should be installed stably. Spring
washers and flat washers should be installed correctly.
z
The insulation accessories between supports and cabinets must satisfy the
insulation requirements. Self-made bases are recommended to be insulated from
the ground or the cabinets.
z
The entire row of cabinets should be arranged closely and neatly. The vertical
deviation should be less than 3 mm (0.1 in.)
z
The cabinet doors at the primary walkway side should be in a straight line. The
error must be less than 5 mm (0.2 in.).
z
The surface of the entire row of cabinets should be on the same plane. Adjacent
cabinets should be closely arranged.
z
All the bolts should be fastened with spring washers and flat washers.
z
Make sure that no component is deformed.