Installation Manual
H3C S7500 Series Ethernet Switches
Appendix A B68-22 Cabinet Installation
A-13
(1) Anchor strip retaining nut
(2) Anchor strip
(3) Cabinet foot
(4) Insulating washer of the
strip
(5) M12 × 70 bolt
(6) Spring washer 12
(7) 12 big flat washer
(8) Insulation washer
(9) Expansion tube
(10) Expansion nut
Figure A-14
Install anchor strips
III. Fixing the retaining nuts of the anchor strips
Fasten the retaining nut on the anchor strip as shown in area B in Figure A-14.
A.2.7 Testing Insulation
Switch the multimeter to Mohm range and measure the resistance between the
fastening bolts M12 × 70 and the anchor strips.
If the resistance is larger than five Mohm, you can finish installation. If not, remove all
anchor strip parts, check that the insulation washers are installed and without damage,
reinstall, and measure insulation until the requirement is satisfied. Figure A-15 and
Figure A-16 illustrate how to install a single and two cabinets on the cement floor
respectively.