Rev. 1.1 of 16/03/2021 - Application: GID
values. Once completed, Save.
19.
The update procedure is now completed and the system must now be restarted correctly by
following the initial start-up procedure described in the relevant section.
Note: if the message “DSP1 Update Failed” or “DSP2 Updated Failed” appear during the update, the
firmware update has not been successful. Therefore, it is necessary to switch off the system by first
lowering the AC switch and then the switches located on the batteries. Wait 3 minutes and follow the
above steps again, starting from point 7.
Note: for more information and to request the firmware update files, please contact the ZCS Azzurro
Technical Support on the toll free number
800 727464
(only in Italy).
6.4.5.
Energy Statistics (Energy statistic)
To enter the screen containing the energy statistics of the system, go back to the main interface and
press the “Menu/Back” key, scroll down with the arrow to point “5. Energy Statistics” and enter with the
“OK” key. This interface shows the data relating to the generation of the photovoltaic system and to the
consumption of the utility in a certain time interval. Press the “Up” and “Down” keys to scroll through
the different time periods: day, week, month, year and life cycle.
An example of the daily statistics screen is shown below.
5.Energy Statistics
Today
PV prod.
10.00KWh
SelfCon
8.00KWh
80%
Export
2.00KWh
20%
Consump. 32.00KWh
SelfCon
7.00KWh
21.87%
Amount
25.00KWh
78.13%