background image

48

To clear an event:

1. Click on the 

down arrow

button in the event number [“Select 1-20”]

field, and select the event number.

2. Click on the 

down arrow

button in the 

Month

field.

3. Click on 

Clear

.

4. Click on 

Set Vacation Schedule

.

To override an event, if you have signage or other units
that will operate during a vacation period:

1. In the 

Thermostats below on Vacation Schedule

column, click

on each thermostat address that you wish to override. Notice that,
when you click on an address, it moves to the 

Override Vacation

2. Click on 

Confirm Override

To print the Vacation event schedule:

1. Click on the 

Print

button.

Allocating Thermostats to Specific Units for use
with ZonexCommander (Plus) only

The ZONED UNITS screen is only applicable to 

ZonexCommander (Plus)

software. It is used to configure, allocate and display thermostats assigned
to their specific 

RMOD

controllers. Each Command Center can support

up to four 

RMODs

. The 

RMODs

are designated as Units #92 – #95.

1. Click on the ZONED UNITS Tab.  
2. Verify that all thermostat/device address numbers appear in the

3. Select the 

RMOD

#92 radio button, and highlight the thermostat

address numbers to be assigned to that 

RMOD

(one or more addresses

may be highlighted). 
NOTE:  When 

DIGICOM

DIGIHP

thermostats or 

RLYCOM

devices

are part of the installation, they must be addressed above #05 (5).

4. Click on Add.  
5. It is important to confirm that the correct thermostats are assigned to

6. Repeat steps 1-5 to allocate thermostats to each RMOD.
7. If an address has been assigned in error, simply highlight the address

number and click on the Remove button. This returns the thermostat
to the Add/Remove column. Reassign the address to the appropriate unit.

8. After all addresses have been assigned to the corresponding RMOD,

click on the Set Zoned Units button on the lower left of the screen.

9. Repeat these procedures for each RMOD #93, #94 and #95 when

10. When the hourglass returns to the arrow cursor on the ZONED UNITS

screen, close the 

ZonexCommander (Plus)

program on the computer;

and recycle power on the Command Center and 

RMOD(s)

.

11. Bring up the 

ZonexCommander (Plus)

program again, and direct-

connect to the system.

12. Go the the REVIEW screen, and verify all termostats are indicating

temperatures.

SYSTEM START-UP PROCEDURE

Schedule

column 

(see Fig. 27)

.  

Fig. 27

ZONED UNITS Screen – 

Fig. 28

Fig. 28

Fig. 29

Fig. 30

that 

RMOD

(see Fig. 29)

.

applicable 

(see Fig. 30)

.

Add/Remove left column 

(see Fig. 28)

Содержание ZonexCommander

Страница 1: ...1 Installation and Applications Manual Part ZCMAN ZonexCommander ZonexCommander Plus Network All Your HVAC Equipment Centralized DDC Communications for Stand Alone HVAC and Zoned Systems Rev Oct 2014...

Страница 2: ...view 16 Sequence Of Operation 17 18 Command Center ZonexCommander Plus 19 Installation Instructions 20 ModStat Thermostat and Supplemental Heat Applications 21 22 Sequence Of Operation 23 RMOD Termina...

Страница 3: ...Zonex is designed to network one or multiple zoned units on one two wire twisted pair for remote communications over the Internet in buildings too large for multiple programmable thermostats but too...

Страница 4: ...provide expansion capability to to 20 devices ModStat MODS2 DIGICOM thermostats and for multiple zoned HVAC systems Each Command Center supports up For use with ZonexCommander Plus systems only capac...

Страница 5: ...pumps blowers lighting etc The devices to be cycled ON and OFF by programmed schedules in the Commander software Status is displayed on the REVIEW screen for dedicated address from 01 to 20 The load a...

Страница 6: ...es are controlled with a relay device RLYCOM Each of these devices can be scheduled through the simple Windows based ZonexCommander software and communicate to the Command Center via a daisy chained 2...

Страница 7: ...oftops or split systems COMMUNICATING ACCESSORIES Optional STAND ALONE EQUIPMENT COMMAND CENTER 21 to 80 additional 20 Thermostats Stand Alone Equipment SENDCOM Duct Temperature Sensor 1 per HVAC unit...

Страница 8: ...hen Emergency Heat is selected Y1 and Y2 are de energized and W2 and G are energized When the DIGIHP thermostat is configured for O reversing valve on an active heat call the O B output will be de ene...

Страница 9: ...strips or solder NOTE for systems with potential electrical interference such as large transformers VFDs etc shielded twisted pair Belden 8450 may be used for the communications loop ZONEXCOMMANDER IN...

Страница 10: ...t side terminal block is for the RX TX communication circuits There are two sets of RX TX terminals on the base to make daisy chain wiring from device to device straightforward and simple 1 Use minimu...

Страница 11: ...cool call when the space temperature rises 1 above the cool setpoint Y2 will energize when the space temperature rises 2 above the cool setpoint When the room temperature is less than 2 from setpoint...

Страница 12: ...RY SENSOR CALIBRATION R12 OUTSIDE AIR OA POWER LED INDICATOR MAIN CONTROL CHIP ZONEXCOMMANDER USB COMPUTER COMMUNICATION RS 485 TWISTED PAIR POLARITY SENSITIVE BELDEN 8740 OUTDOOR AIR SENSOR TERMINAL...

Страница 13: ...13 ZONEXCOMMANDER WIRING OVERVIEW ROOFTOP UNITS UP TO 20 PER COMMAND CENTER...

Страница 14: ...dampers based on zone demand The ZonexCommander Plus system can be applied to existing HVAC systems or new installations providing central control of HVAC operations using Windows based ZonexCommande...

Страница 15: ...15 ZONEXCOMMANDER PLUS COMPONENT SELECTION GUIDE...

Страница 16: ...o be cycled The W1 output signal is connected to the heating device input terminal and the coil of the fan relay This is required for electric heat and gas furnaces with no fan control See Fig 2 on a...

Страница 17: ...ommunicate a heat mode call to the is two degrees or more below room temperature ModStat will modulate the damper to 100 open If the room temperature is within two degrees of setpoint the ModStat will...

Страница 18: ...Release button 1 Push UP button until display shows H 2 Current setpoint will be displayed 3 Push UP or DN button until desired setpoint is displayed 4 Release button operation A shorted sensor or wir...

Страница 19: ...SENSOR CALIBRATION R12 OUTSIDE AIR POWER LED INDICATOR MAIN CONTROL CHIP ZONEX COMMANDER PLUS COMMUNICATION RS 485 TWISTED PAIR POLARITY SENSITIVE BELDEN 8740 SENSOR TERMINAL OA OUTSIDE AIR ONLY TERMI...

Страница 20: ...X Wire nuts are never to be used on the communication wire When making connections use screw type terminal strips or solder NOTE for systems with potential electrical interference such as large transf...

Страница 21: ...After setting the address the thermostat will automatically go back to normal operation and the setpoint temperature will replace the address number just programmed Manual Operation Adjusting Setpoint...

Страница 22: ...hen the space temperaturemeetstheheatsetpoint When configured for Reheat if the space temperature drops 1 below modulate the damper open The heat call will terminate when the space system goes into th...

Страница 23: ...t and 75 F cool as measured by the MIX Air sensor in the return air TEMPERATURE LIMITS AND STAGING The RMOD monitors the leaving air temperature for staging and Hi Low 145 F Staging is based on the li...

Страница 24: ...NSTALLED STATUS LEDs PWR1 Y1 Y2 W1 and O B W2 G 3 4 5 6 7 8 10 9 11 TERMINAL DESIGNATIONS TX Data transmit RX Data receive RA Return air sensor Gas Electric G Fan output W2 Stage 2 heat output W1 Stag...

Страница 25: ...heat elements Heat Pump AHU Addressing Calibration button until the correct address appears and release 2 Energize the FAN only and check RMOD display calibration adjust calibration 4 Return air temp...

Страница 26: ...26 RMOD WIRING OVERVIEW All RX communication wires must be connected to the RX terminals All TX communication wires must be connected to the TX terminals The RX and TX wires should never intersect...

Страница 27: ...sensor controls low and high temperature limits and heat cool staging RA return air sensor controls unit operation in communication failure mode Keep sensor wires and power wires separate NOTE Shorte...

Страница 28: ...gh the 1 4 hole 5 Attach the SENDCOM assembly to the duct or plenum with the sheet metal screws provided 6 Locate the position in the return duct or plenum for the return sensor and drill a 1 4 hole s...

Страница 29: ...will be seen on address 1 2 3 and 4 current room temperatures On ZonexCommander Plus systems a SENDCOM cannot be addressed for thermostats 1 2 3 or 4 so start addressing any stand alone equipment in a...

Страница 30: ...TION When the RLYCOM is in the Occupied mode the on board relays are energized In the Unoccupied mode the relays are de energized The mode status is displayed on the REVIEW screen of the Commander pro...

Страница 31: ...hart 0 1 friction loss per 100 of duct All CFMs listed are approximate For accurate selection use duct sizing table or device MEDIUM PRESSURE STMPD MODSTAT L D W SIZE 6 8 10 12 14 16 6 8 10 12 14 16 D...

Страница 32: ...r drive time open and close is 90 seconds RECTANGULAR MEDIUM PRESSURE ZONE DAMPERS Zonex Systems rectangular medium pressure dampers are recommended for systems under 7 5 tons with a maximum different...

Страница 33: ...that modulates up and down to control air and throw remain constant This keeps the air hugging the ceiling which maximizes room air mixing and minimizes the waterfall effect ZONE DAMPERS RECTANGULAR D...

Страница 34: ...n should be applied to the round pipe and be butted against the hat section do not insulate the motor The motor generates enough heat so that no condensation will develop on it 5 Remember to allow a 1...

Страница 35: ...undersize the bypass damper ROUND BYPASS DAMPER SELECTION The Zonex Systems STMPD damper is used for round bypass applications When you know the bypass CFM requirements use the ROUND BYPASS SELECTION...

Страница 36: ...2000 13333 14667 16000 36 9000 10500 12000 13500 15000 16500 18000 40 10000 11667 13333 15000 16667 18333 20000 44 11000 12833 14667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 2400...

Страница 37: ...ol IPC and air 3 Do not install the bypass damper outside dedicated 24vac 40VA transformer 2 Bypass damper and controller are powered by a recommended for 100 of system CFM system and not undersized B...

Страница 38: ...ve Y outputs to unit on the zone control board and to Note 1 To open all dampers it may be necessary to translates to inches of W C one next to the potentiometer The Voltage reading the leads on the C...

Страница 39: ...CD into the computer drive and note which drive is being used 2 Click on My Computer 1 Place Systems Software Master CD in the CD drive Installing System Software 4 Under the General Tab for propertie...

Страница 40: ...events for each thermostat and RLYCOM Zoned Units Tab Used only with ZonexCommander Plus allocates thermostats to their respective units when multiple units are included in the system SYSTEM START UP...

Страница 41: ...store the password NOTE Your password should be retained elsewhere If it is lost the program will have to be re installed and all information re entered Adding Modifying or Deleting Records To add or...

Страница 42: ...ord to be deleted f Click on Records g Click on Delete h Click on File then click on Save i Click on Exit to return to the WELCOME Tab Connecting to the Zonex System 1 Click on the Connect Now button...

Страница 43: ...nd Settings to place this information into memory Date Time will appear on the upper right of the screen 2 Click on the right or left arrow next to the month and year to select the current month or cl...

Страница 44: ...by returning to the REVIEW Tab If the thermostat number you selected is Red it is locked if it is Black it is unlocked If necessary repeat the sequence above to change to desired setting Reviewing Sys...

Страница 45: ...setting 6 SENDCOM communications are used to display RA SA temperatures from stand alone units a Place the cursor directly over a Current Room Temperature thermostat number with a SENDCOM attached an...

Страница 46: ...isplay thermostat address numbers and names and click on an address b After selecting the desired address the current Occupied and Unoccupied temperature setpoints for that thermostat will be 4 After...

Страница 47: ...y a Select the thermostat or RLYCOM address from the pull down menu under Select Thermostat b Click on the radio button next to the day of the week to be scheduled Schedule each day individually After...

Страница 48: ...he thermostat address numbers to be assigned to that RMOD one or more addresses may be highlighted NOTE When DIGICOM DIGIHP thermostats or RLYCOM devices are part of the installation they must be addr...

Страница 49: ...nex Systems 6 After the logging commences you may minimize the Zonex program in order to use other computer functions but do not turn off the computer or trending program during data collection This w...

Страница 50: ...ge to return to Page 1 of the Trending program Then select another thermostat you wish to analyze by using the drop down arrow and the data will be retrieved quickly 13 After the data is collected if...

Страница 51: ...thermostat address add 70 B Verify device has the correct address For A Verify device is powered up 1 SENDCOM reporting 0 on Read Sensors window SENDCOM Common Ground Phasing E Check polarity of R C...

Страница 52: ...00 228 2966 M F 6 30 AM 5 00 PM PST DAY OCC DAY UNOCC NIGHT OCC NIGHT UNOCC DAY ADR NAME H C H C H C H C MON TUES WED THUR FRI SAT SUN MON TUES WED THUR FRI SAT SUN MON TUES WED THUR FRI SAT SUN MON T...

Страница 53: ......

Страница 54: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations Part ZCMAN ZonexCommander Plus Network All Your HVAC Equipment Centralized DDC Communication...

Отзывы: