background image

21

DESCRIPTION

The LCD 

ModStat

is available for the 

ZonexCommander

The unique grey display backlight is constantly illuminated in the Occupied
mode. The display backlight will go out in the Unoccupied mode. If any
button is pressed while the thermostat is in the Unoccupied mode, the
backlight will illuminate for 5 seconds. The backlight will also be
illuminated when the thermostat is in the 2-hour override mode.

INSTALLATION 
Thermostat and terminal base

1.  The thermostat is to be installed on an interior wall, away from drafts,

supply air currents and direct sunlight or any heat generating source.

2.  To remove the thermostat cover, grasp the cover at the top and pull

straight off; do not pivot the cover from the base.

3.  Install the thermostat terminal base to the wall using the provided

anchors and screws.  The thermostat can also be mounted on a 2x4
electrical box using two #6-32” screws.

WIRING

The Zonex Systems 

ModStat

and 

MODS2

thermostats have been specifically

designed to make wall mounting and wire connections very easy. The
thermostat terminal base has two separate terminal blocks: the left side
terminal block is for the 24vac control circuits, and the right side terminal
block is for the RX TX communication circuits. There are two sets of RX
TX terminals on the base to make daisy chain wiring from device to device
straightforward and simple.  
1. Use minimum 18-gauge AWG thermostat wire for the 24vac control

circuits. The load on the auxiliary heat circuit must not exceed 1 amp
at 24vac. The voltage range on R and C must not exceed 28vac. 

2. Connect the communication wires to the RX TX terminals. There are

2 sets of RX TX terminals for “daisy chain” installation of this circuit.
The communication wire specification is: twisted pair (Belden 8740)
or shielded twisted pair wire (Belden 8450). Refer to manual (ZCMAN).
NOTE: When using shielded twisted pair wire (Belden 8450), just
connect the shield conductors together, as there is no electrical
connection on the thermostat base terminals. The shield will be landed
on the Command Center on the G or TR2 terminal.

3. On the 

ModStat

, connect the damper control wires from MC, RC and RO to

the actuator terminals. For 

MODS2

, connect MC and RC to the damper motor.

4. Auxiliary Heat – The 

ModStat

and 

MODS2

provide a 24vac signal

gized when the space temperature is 2° below the heat setpoint. The
signal is de-energized at setpoint temperature.

CONFIGURATION
Addressing

(1-20). Each thermostat must have a unique address from 1 to 20.

1. Press and hold the 

Menu

button until you see the system mode display

on the lower right begin to scroll and change modes; then press and
hold the 

Heat/Cool

button with the 

Menu

button. 

2. When the display shows “address,” release the 

Menu

and 

Heat/Cool

buttons; and press the 

UP

or 

DN

button until the correct address is

displayed in the upper right of the display.   

3. After setting the address, the thermostat will automatically go back to

normal operation; and the setpoint temperature will replace the
address number just programmed.

Manual Operation - Adjusting Setpoints

The Heat or Cool setpoints can be displayed by pressing the 

Heat/Cool

button; the setpoint will be displayed on the upper right of the display.

Heat

– If “Heat Setting” is displayed on the top right of the display,

simply press the 

UP

or 

DN

button to change the heat setpoint. If “Cool

Setting” is displayed and you want to change the Heat setpoint, press and
hold the 

Heat/Cool

button twice to change from “Cool Setting” to “Heat

Setting.” Then press the 

UP

or 

DN

button to change the setpoint. 

Cool

– If “Cool Setting” is displayed on the top right of the display, simply

press the 

UP

or 

DN

button to change the cool setpoint. If “Heat Setting”

is displayed and you want to change the Cool setpoint, press and hold the

Heat/Cool

button twice to change from “Heat Setting” to “Cool Setting.”

Then press the 

UP

or 

DN

button to change the setpoint. 

Changing Mode

The thermostats are auto changeover, but specific modes may be selected.
Auto mode is the default.

Heat 

only – Press and hold the 

Menu

button, and note the mode display

begin to change. Press the 

Select

button when Heat is displayed.

Cool 

only – Press and hold the 

Menu

button, and note the mode display

begin to change. Press the 

Select

button when Cool is displayed.

System Off

– Press and hold the 

Menu

button, and note the mode

display begin to change. Press the 

Select

button when Off is displayed.

Auto

mode – Press and release the 

Menu

button.

Override

When the thermostat displays “Unoccupied” (top of display), a 2-hour
temporary override may be initiated by pressing the Override/

Select

button.

When additional override time is required, press the Override/

Select

button again.

Display Temperature Calibration   

Thermostats are calibrated at the factory and should require no further
adjustment. However, the display space temperature may be field cali-
brated by the following procedure:
1. Press and hold the 

Heat/Cool

and 

Select

buttons together; then press

2. To lower the temperature display, press the 

DN

button once, after

pressing the 

Heat/Cool

and 

Select

buttons. This makes a 1° change.

ModStat / MODS2 THERMOSTATS

with the System 2000 

GEN II

product. The 

ModStat

(Plus)

DDC control system. It is also utilized

version drives medium pressure, power open / power
close dampers for modulating applications.  The 

MODS2

version drives low pressure, power close /

spring open dampers for 2-position systems, which are
2000 CFM or less.

NOTE:  An Air Proving Switch must be wired into the “AUX” output to 
protect the electric heating devices.

output on the "AUX” terminal for Auxiliary Heat. This signal is ener-

including Fan Powered VAV boxes.   The terminal base provides a 
24 volt output on terminal “AUX” for the heat elements and the fan relay 

5.  Reheat - The 

ModStat

can be field configured for Reheat applications,

circuit (if applicable).  

and release the 

UP

 button to increase the display temperature by 1°.

Содержание ZonexCommander

Страница 1: ...1 Installation and Applications Manual Part ZCMAN ZonexCommander ZonexCommander Plus Network All Your HVAC Equipment Centralized DDC Communications for Stand Alone HVAC and Zoned Systems Rev Oct 2014...

Страница 2: ...view 16 Sequence Of Operation 17 18 Command Center ZonexCommander Plus 19 Installation Instructions 20 ModStat Thermostat and Supplemental Heat Applications 21 22 Sequence Of Operation 23 RMOD Termina...

Страница 3: ...Zonex is designed to network one or multiple zoned units on one two wire twisted pair for remote communications over the Internet in buildings too large for multiple programmable thermostats but too...

Страница 4: ...provide expansion capability to to 20 devices ModStat MODS2 DIGICOM thermostats and for multiple zoned HVAC systems Each Command Center supports up For use with ZonexCommander Plus systems only capac...

Страница 5: ...pumps blowers lighting etc The devices to be cycled ON and OFF by programmed schedules in the Commander software Status is displayed on the REVIEW screen for dedicated address from 01 to 20 The load a...

Страница 6: ...es are controlled with a relay device RLYCOM Each of these devices can be scheduled through the simple Windows based ZonexCommander software and communicate to the Command Center via a daisy chained 2...

Страница 7: ...oftops or split systems COMMUNICATING ACCESSORIES Optional STAND ALONE EQUIPMENT COMMAND CENTER 21 to 80 additional 20 Thermostats Stand Alone Equipment SENDCOM Duct Temperature Sensor 1 per HVAC unit...

Страница 8: ...hen Emergency Heat is selected Y1 and Y2 are de energized and W2 and G are energized When the DIGIHP thermostat is configured for O reversing valve on an active heat call the O B output will be de ene...

Страница 9: ...strips or solder NOTE for systems with potential electrical interference such as large transformers VFDs etc shielded twisted pair Belden 8450 may be used for the communications loop ZONEXCOMMANDER IN...

Страница 10: ...t side terminal block is for the RX TX communication circuits There are two sets of RX TX terminals on the base to make daisy chain wiring from device to device straightforward and simple 1 Use minimu...

Страница 11: ...cool call when the space temperature rises 1 above the cool setpoint Y2 will energize when the space temperature rises 2 above the cool setpoint When the room temperature is less than 2 from setpoint...

Страница 12: ...RY SENSOR CALIBRATION R12 OUTSIDE AIR OA POWER LED INDICATOR MAIN CONTROL CHIP ZONEXCOMMANDER USB COMPUTER COMMUNICATION RS 485 TWISTED PAIR POLARITY SENSITIVE BELDEN 8740 OUTDOOR AIR SENSOR TERMINAL...

Страница 13: ...13 ZONEXCOMMANDER WIRING OVERVIEW ROOFTOP UNITS UP TO 20 PER COMMAND CENTER...

Страница 14: ...dampers based on zone demand The ZonexCommander Plus system can be applied to existing HVAC systems or new installations providing central control of HVAC operations using Windows based ZonexCommande...

Страница 15: ...15 ZONEXCOMMANDER PLUS COMPONENT SELECTION GUIDE...

Страница 16: ...o be cycled The W1 output signal is connected to the heating device input terminal and the coil of the fan relay This is required for electric heat and gas furnaces with no fan control See Fig 2 on a...

Страница 17: ...ommunicate a heat mode call to the is two degrees or more below room temperature ModStat will modulate the damper to 100 open If the room temperature is within two degrees of setpoint the ModStat will...

Страница 18: ...Release button 1 Push UP button until display shows H 2 Current setpoint will be displayed 3 Push UP or DN button until desired setpoint is displayed 4 Release button operation A shorted sensor or wir...

Страница 19: ...SENSOR CALIBRATION R12 OUTSIDE AIR POWER LED INDICATOR MAIN CONTROL CHIP ZONEX COMMANDER PLUS COMMUNICATION RS 485 TWISTED PAIR POLARITY SENSITIVE BELDEN 8740 SENSOR TERMINAL OA OUTSIDE AIR ONLY TERMI...

Страница 20: ...X Wire nuts are never to be used on the communication wire When making connections use screw type terminal strips or solder NOTE for systems with potential electrical interference such as large transf...

Страница 21: ...After setting the address the thermostat will automatically go back to normal operation and the setpoint temperature will replace the address number just programmed Manual Operation Adjusting Setpoint...

Страница 22: ...hen the space temperaturemeetstheheatsetpoint When configured for Reheat if the space temperature drops 1 below modulate the damper open The heat call will terminate when the space system goes into th...

Страница 23: ...t and 75 F cool as measured by the MIX Air sensor in the return air TEMPERATURE LIMITS AND STAGING The RMOD monitors the leaving air temperature for staging and Hi Low 145 F Staging is based on the li...

Страница 24: ...NSTALLED STATUS LEDs PWR1 Y1 Y2 W1 and O B W2 G 3 4 5 6 7 8 10 9 11 TERMINAL DESIGNATIONS TX Data transmit RX Data receive RA Return air sensor Gas Electric G Fan output W2 Stage 2 heat output W1 Stag...

Страница 25: ...heat elements Heat Pump AHU Addressing Calibration button until the correct address appears and release 2 Energize the FAN only and check RMOD display calibration adjust calibration 4 Return air temp...

Страница 26: ...26 RMOD WIRING OVERVIEW All RX communication wires must be connected to the RX terminals All TX communication wires must be connected to the TX terminals The RX and TX wires should never intersect...

Страница 27: ...sensor controls low and high temperature limits and heat cool staging RA return air sensor controls unit operation in communication failure mode Keep sensor wires and power wires separate NOTE Shorte...

Страница 28: ...gh the 1 4 hole 5 Attach the SENDCOM assembly to the duct or plenum with the sheet metal screws provided 6 Locate the position in the return duct or plenum for the return sensor and drill a 1 4 hole s...

Страница 29: ...will be seen on address 1 2 3 and 4 current room temperatures On ZonexCommander Plus systems a SENDCOM cannot be addressed for thermostats 1 2 3 or 4 so start addressing any stand alone equipment in a...

Страница 30: ...TION When the RLYCOM is in the Occupied mode the on board relays are energized In the Unoccupied mode the relays are de energized The mode status is displayed on the REVIEW screen of the Commander pro...

Страница 31: ...hart 0 1 friction loss per 100 of duct All CFMs listed are approximate For accurate selection use duct sizing table or device MEDIUM PRESSURE STMPD MODSTAT L D W SIZE 6 8 10 12 14 16 6 8 10 12 14 16 D...

Страница 32: ...r drive time open and close is 90 seconds RECTANGULAR MEDIUM PRESSURE ZONE DAMPERS Zonex Systems rectangular medium pressure dampers are recommended for systems under 7 5 tons with a maximum different...

Страница 33: ...that modulates up and down to control air and throw remain constant This keeps the air hugging the ceiling which maximizes room air mixing and minimizes the waterfall effect ZONE DAMPERS RECTANGULAR D...

Страница 34: ...n should be applied to the round pipe and be butted against the hat section do not insulate the motor The motor generates enough heat so that no condensation will develop on it 5 Remember to allow a 1...

Страница 35: ...undersize the bypass damper ROUND BYPASS DAMPER SELECTION The Zonex Systems STMPD damper is used for round bypass applications When you know the bypass CFM requirements use the ROUND BYPASS SELECTION...

Страница 36: ...2000 13333 14667 16000 36 9000 10500 12000 13500 15000 16500 18000 40 10000 11667 13333 15000 16667 18333 20000 44 11000 12833 14667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 2400...

Страница 37: ...ol IPC and air 3 Do not install the bypass damper outside dedicated 24vac 40VA transformer 2 Bypass damper and controller are powered by a recommended for 100 of system CFM system and not undersized B...

Страница 38: ...ve Y outputs to unit on the zone control board and to Note 1 To open all dampers it may be necessary to translates to inches of W C one next to the potentiometer The Voltage reading the leads on the C...

Страница 39: ...CD into the computer drive and note which drive is being used 2 Click on My Computer 1 Place Systems Software Master CD in the CD drive Installing System Software 4 Under the General Tab for propertie...

Страница 40: ...events for each thermostat and RLYCOM Zoned Units Tab Used only with ZonexCommander Plus allocates thermostats to their respective units when multiple units are included in the system SYSTEM START UP...

Страница 41: ...store the password NOTE Your password should be retained elsewhere If it is lost the program will have to be re installed and all information re entered Adding Modifying or Deleting Records To add or...

Страница 42: ...ord to be deleted f Click on Records g Click on Delete h Click on File then click on Save i Click on Exit to return to the WELCOME Tab Connecting to the Zonex System 1 Click on the Connect Now button...

Страница 43: ...nd Settings to place this information into memory Date Time will appear on the upper right of the screen 2 Click on the right or left arrow next to the month and year to select the current month or cl...

Страница 44: ...by returning to the REVIEW Tab If the thermostat number you selected is Red it is locked if it is Black it is unlocked If necessary repeat the sequence above to change to desired setting Reviewing Sys...

Страница 45: ...setting 6 SENDCOM communications are used to display RA SA temperatures from stand alone units a Place the cursor directly over a Current Room Temperature thermostat number with a SENDCOM attached an...

Страница 46: ...isplay thermostat address numbers and names and click on an address b After selecting the desired address the current Occupied and Unoccupied temperature setpoints for that thermostat will be 4 After...

Страница 47: ...y a Select the thermostat or RLYCOM address from the pull down menu under Select Thermostat b Click on the radio button next to the day of the week to be scheduled Schedule each day individually After...

Страница 48: ...he thermostat address numbers to be assigned to that RMOD one or more addresses may be highlighted NOTE When DIGICOM DIGIHP thermostats or RLYCOM devices are part of the installation they must be addr...

Страница 49: ...nex Systems 6 After the logging commences you may minimize the Zonex program in order to use other computer functions but do not turn off the computer or trending program during data collection This w...

Страница 50: ...ge to return to Page 1 of the Trending program Then select another thermostat you wish to analyze by using the drop down arrow and the data will be retrieved quickly 13 After the data is collected if...

Страница 51: ...thermostat address add 70 B Verify device has the correct address For A Verify device is powered up 1 SENDCOM reporting 0 on Read Sensors window SENDCOM Common Ground Phasing E Check polarity of R C...

Страница 52: ...00 228 2966 M F 6 30 AM 5 00 PM PST DAY OCC DAY UNOCC NIGHT OCC NIGHT UNOCC DAY ADR NAME H C H C H C H C MON TUES WED THUR FRI SAT SUN MON TUES WED THUR FRI SAT SUN MON TUES WED THUR FRI SAT SUN MON T...

Страница 53: ......

Страница 54: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations Part ZCMAN ZonexCommander Plus Network All Your HVAC Equipment Centralized DDC Communication...

Отзывы: