OPERATION

When heating or cooling calls are sent to the 

RMOD

Relay Module by the

thermostat, the 

RMOD

will treat these calls as votes to determine mode

When configured for Heat Pump operation, the cut-out is automatically

COOL CALLS

If the majority of calls are for cooling, the 

RMOD

will energize Y1 and G

for 1st stage cooling. After 4 minutes, the 

RMOD

will check the leaving

provided for compressor safety.

HEAT CALLS

If the majority of calls are for heating, the 

RMOD

will energize W1 for 1st

stage heating. The 

RMOD

will bring on additional stages in 3-minute

increments. See Gas Electric and Heat Pump staging.

CHANGEOVER

If the system is running in one mode and the majority of calls changes
to the other mode, a timer will start. The 

RMOD

will give the current

operating mode another 4 minutes to try to satisfy the zone(s). It will
then go into the purge cycle before switching modes to the majority.

PURGE MODE

When a heat or cool call is satisfied, or before changing modes, the

RMOD

will go into a 3-minute purge cycle. The call for heat or cool will

be removed, and the dampers close.

VENTILATION MODES

The 

RMOD

can be field configured for FAN Constant in the Occupied

mode or FAN Automatic. When all zones are satisfied, dampers will
modulate to 50% open.

EMERGENCY HEAT

Selected by the on-board switch or remote switch.

COMMUNICATION FAILURE

If the 

RMOD

loses communications, it will then control the HVAC unit

based on the return air temperature. The 

RMOD

will maintain 70° F heat

and 75° F cool as measured by the MIX Air sensor in the return air.

TEMPERATURE LIMITS AND STAGING

The 

RMOD

monitors the leaving air temperature for staging and Hi /Low

145° F. Staging is based on the limit settings.

Gas Electric & Heat Pump

Example:

Gas Electric
Heating

W2 cut-in temperature is high limit minus 15° F (145° - 15°

= 130° F). The W2 cut-out is cut-in plus 10° F (130° + 10° = 140° F).
Example:
Adjustable high limit = 145° F
W2 Cut-in = 130° F (high limit minus fifteen)
W2 Cut-out = 140° F (cut-in plus ten)
W1 cut out = 145°

Heat Pump
Heating

– When the 

RMOD

is configured for HP operation, the high

cut-out is automatically set to 121°.
• W2 energizes when the SA temperature is 88° or less after 4 minutes

of run time. W2 de-energizes when the SA temperature rises to 100°.

• Y2 energizes when the SA temperature is below 100° after 2 minutes

of run time and de-energizes above 115°.

• Y1 cuts out for 4 minutes when the SA temperature is above 120°.

TEMPERATURE LIMIT ADJUSTMENT

The high and low cut-out temperatures are field adjustable.

HVAC unit operation.

RMOD SEQUENCE OF OPERATION

NOTE: The RA and LV AIR sensors (P# 

LAT

) must be installed for

of operation. Adjustable factory limits are 45°F cool and 145°F heat.

set for 121° heat.

at 45° F. Four-minute minimum run and four-minute off delays are

limit. The adjustable factory low limit is 45° F and the high limit is

Cooling

Y2 cut-in temperature is low limit plus 10°F (45°+ 10°= 55°F).

The Y2 cut-out is cut-in minus 8° F (55° – 8° = 47° F).

Adjustable low limit = 45° F
Y2 Cut-in = 55° F (low limit plus ten)
Y2 Cut-out = 47° F (cut-in minus eight)

energize. Y2 will stage off at 47° F and Y1 will stage off on low temperature

air temperature. If the leaving air temperature is above 55° F, then Y2 will

Содержание ZonexCommander

Страница 1: ...1 Installation and Applications Manual Part ZCMAN ZonexCommander ZonexCommander Plus Network All Your HVAC Equipment Centralized DDC Communications for Stand Alone HVAC and Zoned Systems Rev Oct 2014...

Страница 2: ...view 16 Sequence Of Operation 17 18 Command Center ZonexCommander Plus 19 Installation Instructions 20 ModStat Thermostat and Supplemental Heat Applications 21 22 Sequence Of Operation 23 RMOD Termina...

Страница 3: ...Zonex is designed to network one or multiple zoned units on one two wire twisted pair for remote communications over the Internet in buildings too large for multiple programmable thermostats but too...

Страница 4: ...provide expansion capability to to 20 devices ModStat MODS2 DIGICOM thermostats and for multiple zoned HVAC systems Each Command Center supports up For use with ZonexCommander Plus systems only capac...

Страница 5: ...pumps blowers lighting etc The devices to be cycled ON and OFF by programmed schedules in the Commander software Status is displayed on the REVIEW screen for dedicated address from 01 to 20 The load a...

Страница 6: ...es are controlled with a relay device RLYCOM Each of these devices can be scheduled through the simple Windows based ZonexCommander software and communicate to the Command Center via a daisy chained 2...

Страница 7: ...oftops or split systems COMMUNICATING ACCESSORIES Optional STAND ALONE EQUIPMENT COMMAND CENTER 21 to 80 additional 20 Thermostats Stand Alone Equipment SENDCOM Duct Temperature Sensor 1 per HVAC unit...

Страница 8: ...hen Emergency Heat is selected Y1 and Y2 are de energized and W2 and G are energized When the DIGIHP thermostat is configured for O reversing valve on an active heat call the O B output will be de ene...

Страница 9: ...strips or solder NOTE for systems with potential electrical interference such as large transformers VFDs etc shielded twisted pair Belden 8450 may be used for the communications loop ZONEXCOMMANDER IN...

Страница 10: ...t side terminal block is for the RX TX communication circuits There are two sets of RX TX terminals on the base to make daisy chain wiring from device to device straightforward and simple 1 Use minimu...

Страница 11: ...cool call when the space temperature rises 1 above the cool setpoint Y2 will energize when the space temperature rises 2 above the cool setpoint When the room temperature is less than 2 from setpoint...

Страница 12: ...RY SENSOR CALIBRATION R12 OUTSIDE AIR OA POWER LED INDICATOR MAIN CONTROL CHIP ZONEXCOMMANDER USB COMPUTER COMMUNICATION RS 485 TWISTED PAIR POLARITY SENSITIVE BELDEN 8740 OUTDOOR AIR SENSOR TERMINAL...

Страница 13: ...13 ZONEXCOMMANDER WIRING OVERVIEW ROOFTOP UNITS UP TO 20 PER COMMAND CENTER...

Страница 14: ...dampers based on zone demand The ZonexCommander Plus system can be applied to existing HVAC systems or new installations providing central control of HVAC operations using Windows based ZonexCommande...

Страница 15: ...15 ZONEXCOMMANDER PLUS COMPONENT SELECTION GUIDE...

Страница 16: ...o be cycled The W1 output signal is connected to the heating device input terminal and the coil of the fan relay This is required for electric heat and gas furnaces with no fan control See Fig 2 on a...

Страница 17: ...ommunicate a heat mode call to the is two degrees or more below room temperature ModStat will modulate the damper to 100 open If the room temperature is within two degrees of setpoint the ModStat will...

Страница 18: ...Release button 1 Push UP button until display shows H 2 Current setpoint will be displayed 3 Push UP or DN button until desired setpoint is displayed 4 Release button operation A shorted sensor or wir...

Страница 19: ...SENSOR CALIBRATION R12 OUTSIDE AIR POWER LED INDICATOR MAIN CONTROL CHIP ZONEX COMMANDER PLUS COMMUNICATION RS 485 TWISTED PAIR POLARITY SENSITIVE BELDEN 8740 SENSOR TERMINAL OA OUTSIDE AIR ONLY TERMI...

Страница 20: ...X Wire nuts are never to be used on the communication wire When making connections use screw type terminal strips or solder NOTE for systems with potential electrical interference such as large transf...

Страница 21: ...After setting the address the thermostat will automatically go back to normal operation and the setpoint temperature will replace the address number just programmed Manual Operation Adjusting Setpoint...

Страница 22: ...hen the space temperaturemeetstheheatsetpoint When configured for Reheat if the space temperature drops 1 below modulate the damper open The heat call will terminate when the space system goes into th...

Страница 23: ...t and 75 F cool as measured by the MIX Air sensor in the return air TEMPERATURE LIMITS AND STAGING The RMOD monitors the leaving air temperature for staging and Hi Low 145 F Staging is based on the li...

Страница 24: ...NSTALLED STATUS LEDs PWR1 Y1 Y2 W1 and O B W2 G 3 4 5 6 7 8 10 9 11 TERMINAL DESIGNATIONS TX Data transmit RX Data receive RA Return air sensor Gas Electric G Fan output W2 Stage 2 heat output W1 Stag...

Страница 25: ...heat elements Heat Pump AHU Addressing Calibration button until the correct address appears and release 2 Energize the FAN only and check RMOD display calibration adjust calibration 4 Return air temp...

Страница 26: ...26 RMOD WIRING OVERVIEW All RX communication wires must be connected to the RX terminals All TX communication wires must be connected to the TX terminals The RX and TX wires should never intersect...

Страница 27: ...sensor controls low and high temperature limits and heat cool staging RA return air sensor controls unit operation in communication failure mode Keep sensor wires and power wires separate NOTE Shorte...

Страница 28: ...gh the 1 4 hole 5 Attach the SENDCOM assembly to the duct or plenum with the sheet metal screws provided 6 Locate the position in the return duct or plenum for the return sensor and drill a 1 4 hole s...

Страница 29: ...will be seen on address 1 2 3 and 4 current room temperatures On ZonexCommander Plus systems a SENDCOM cannot be addressed for thermostats 1 2 3 or 4 so start addressing any stand alone equipment in a...

Страница 30: ...TION When the RLYCOM is in the Occupied mode the on board relays are energized In the Unoccupied mode the relays are de energized The mode status is displayed on the REVIEW screen of the Commander pro...

Страница 31: ...hart 0 1 friction loss per 100 of duct All CFMs listed are approximate For accurate selection use duct sizing table or device MEDIUM PRESSURE STMPD MODSTAT L D W SIZE 6 8 10 12 14 16 6 8 10 12 14 16 D...

Страница 32: ...r drive time open and close is 90 seconds RECTANGULAR MEDIUM PRESSURE ZONE DAMPERS Zonex Systems rectangular medium pressure dampers are recommended for systems under 7 5 tons with a maximum different...

Страница 33: ...that modulates up and down to control air and throw remain constant This keeps the air hugging the ceiling which maximizes room air mixing and minimizes the waterfall effect ZONE DAMPERS RECTANGULAR D...

Страница 34: ...n should be applied to the round pipe and be butted against the hat section do not insulate the motor The motor generates enough heat so that no condensation will develop on it 5 Remember to allow a 1...

Страница 35: ...undersize the bypass damper ROUND BYPASS DAMPER SELECTION The Zonex Systems STMPD damper is used for round bypass applications When you know the bypass CFM requirements use the ROUND BYPASS SELECTION...

Страница 36: ...2000 13333 14667 16000 36 9000 10500 12000 13500 15000 16500 18000 40 10000 11667 13333 15000 16667 18333 20000 44 11000 12833 14667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 2400...

Страница 37: ...ol IPC and air 3 Do not install the bypass damper outside dedicated 24vac 40VA transformer 2 Bypass damper and controller are powered by a recommended for 100 of system CFM system and not undersized B...

Страница 38: ...ve Y outputs to unit on the zone control board and to Note 1 To open all dampers it may be necessary to translates to inches of W C one next to the potentiometer The Voltage reading the leads on the C...

Страница 39: ...CD into the computer drive and note which drive is being used 2 Click on My Computer 1 Place Systems Software Master CD in the CD drive Installing System Software 4 Under the General Tab for propertie...

Страница 40: ...events for each thermostat and RLYCOM Zoned Units Tab Used only with ZonexCommander Plus allocates thermostats to their respective units when multiple units are included in the system SYSTEM START UP...

Страница 41: ...store the password NOTE Your password should be retained elsewhere If it is lost the program will have to be re installed and all information re entered Adding Modifying or Deleting Records To add or...

Страница 42: ...ord to be deleted f Click on Records g Click on Delete h Click on File then click on Save i Click on Exit to return to the WELCOME Tab Connecting to the Zonex System 1 Click on the Connect Now button...

Страница 43: ...nd Settings to place this information into memory Date Time will appear on the upper right of the screen 2 Click on the right or left arrow next to the month and year to select the current month or cl...

Страница 44: ...by returning to the REVIEW Tab If the thermostat number you selected is Red it is locked if it is Black it is unlocked If necessary repeat the sequence above to change to desired setting Reviewing Sys...

Страница 45: ...setting 6 SENDCOM communications are used to display RA SA temperatures from stand alone units a Place the cursor directly over a Current Room Temperature thermostat number with a SENDCOM attached an...

Страница 46: ...isplay thermostat address numbers and names and click on an address b After selecting the desired address the current Occupied and Unoccupied temperature setpoints for that thermostat will be 4 After...

Страница 47: ...y a Select the thermostat or RLYCOM address from the pull down menu under Select Thermostat b Click on the radio button next to the day of the week to be scheduled Schedule each day individually After...

Страница 48: ...he thermostat address numbers to be assigned to that RMOD one or more addresses may be highlighted NOTE When DIGICOM DIGIHP thermostats or RLYCOM devices are part of the installation they must be addr...

Страница 49: ...nex Systems 6 After the logging commences you may minimize the Zonex program in order to use other computer functions but do not turn off the computer or trending program during data collection This w...

Страница 50: ...ge to return to Page 1 of the Trending program Then select another thermostat you wish to analyze by using the drop down arrow and the data will be retrieved quickly 13 After the data is collected if...

Страница 51: ...thermostat address add 70 B Verify device has the correct address For A Verify device is powered up 1 SENDCOM reporting 0 on Read Sensors window SENDCOM Common Ground Phasing E Check polarity of R C...

Страница 52: ...00 228 2966 M F 6 30 AM 5 00 PM PST DAY OCC DAY UNOCC NIGHT OCC NIGHT UNOCC DAY ADR NAME H C H C H C H C MON TUES WED THUR FRI SAT SUN MON TUES WED THUR FRI SAT SUN MON TUES WED THUR FRI SAT SUN MON T...

Страница 53: ......

Страница 54: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations Part ZCMAN ZonexCommander Plus Network All Your HVAC Equipment Centralized DDC Communication...

Отзывы: