29
12. Set the individual
SENDCOM
address to correlate to the thermostat
for that HVAC unit.
EXAMPLE:
If the
DIGICOM
or
DIGIHP
thermostat has an address of 01,
to address the
SENDCOM,
add 70 to the address number of the thermostat.
This makes the
SENDCOM
address 71. If the address on the
DIGICOM
or
DIGIHP
is 02; add 70 to make the
SENDCOM
address 72, etc.
Applications with
ZonexCommander (Plus)
will not use
SENDCOMs
to see supply and return air temperatures. These are reported from the
RMODs
and will be seen on address 1, 2, 3, and 4 current room
temperatures. On
ZonexCommander (Plus)
systems a
SENDCOM
cannot be addressed for thermostats 1, 2, 3, or 4, so start addressing any
stand alone equipment in a
ZonexCommander (Plus)
system at 75.
13. The
SENDCOM
is calibrated at the factory but can be field calibrated
tiometer for return air.
SENDCOM DESCRIPTION
1
7
1
2
7
2
3
7
3
4
7
4
5
7
5
6
7
6
7
7
7
8
7
8
9
7
9
10
8
0
11
8
1
12
8
2
13
8
3
14
8
4
15
8
5
16
8
6
17
8
7
18
8
8
19
8
9
20
9
0
ADDRESSING
Determine the thermostat address to which the
SENDCOM
will be
THERMOSTAT
TENS
ONES
ADDRESS SENDCOM
applied, and add a value of 70.
by adjusting the R2 potentiometer for Supply Air or the R10 poten-