InZennio Z41
http://www.zennio.com
Tecnical Support:
http://support.zennio.com
90
Number
Size
I/O
Flags
Data Type (DPT)
Functional range
Name
Function
114, 117, 120,
123, 126, 129,
132, 135, 138,
141, 144, 147,
150
2 Bytes
O
C T R - -
DPT_Value_2_Ucount
0 - 65535
[PX][BX] Green Channel
0-100%
2 Bytes
O
C T R - -
-32768 - 32767
-32768 - 32767
[PX][BX] Special Mode Control
Comfort, Standby, Economy and
Building Protection
2 Bytes
O
C T R - -
9.xxx
-671088.64 –
670760.96
[PX][BX] Fan Control
0=Decrease; 1=Increase
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[PX][BX] Mode Control
Heat, Cool, Auto, Fan and Dry
1 Bit
O
C T R - -
DPT_UpDown
0/1
[PX][BX] Mode Control
0 = Cool; 1 = Heat
1 Bit
O
C T R - -
DPT_Switch
0/1
[PX][BX] Temperature Offset Control 0=Decrease; 1=Increase
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 – 670760.00
[PX][BX] Temperature Offset Control Relative Float Value
2 Bytes
I/O
C T R W -
DPT_Value_Tempd
-670760.00 –
670760.00
[PX][BX] Temperature Control
Absolute Float Value
1 Bit
O
C T R - -
DPT_Step
0/1
[PX][BX] Light On/Off
0=Off; 1=On
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[PX][BX] Move Shutter
0=Up; 1=Down
1 Byte
O
C T R - -
DPT_HVACContrMode
0 = Auto
1 = Heat
3 = Cool
9 = Fan
14 = Dry
[PX][BX] Enumerated Control
0...255
1 Bit
O
C T R - -
DPT_Step
0/1
[PX][BX] 2-byte Float Control
-671088.64...670760.96
1 Byte
O
C T R - -
DPT_HVACMode
1 = Comfort
2 = Standby
3 = Economy
4 = Protection
[PX][BX] 2-byte Signed Int Control -32768...32767
1 Byte
I/O
C T R W U
DPT_Scaling
0% - 100%
[PX][BX] 2-byte Unsigned Int Control 0...65535
1 Bit
O
C T R - -
DPT_Switch
0/1
[PX][BX] Percentage Control
0-100%
1 Bit
O
C T R - -
DPT_Switch
0/1
[PX][BX] 1-byte Signed Int Control -128...127
1 Bit
I
C T - W -
DPT_Ack
0/1
[PX][BX] 1-byte Unsigned Int Control 0...255
1 Bit
O
C T R - -
DPT_Trigger
0/1
[PX][BX] Binary Control
1-bit Control
10, 13, 16, 19,
22, 25, 28, 31,
34, 37, 40, 43,
46, 49, 52, 55,
58, 61, 64, 67,
70, 73, 76, 79,
82, 85, 88, 91,
1 Bit
O
C T R - -
DPT_Step
0/1
[PX][BX] Energy Monitor: reset
0=No Action; 1=Reset
1 Bit
O
C T R - -
DPT_Switch
0/1
[PX][BX] Chrono-thermostat: on/off 0=Off; 1=On
4 Bit
O
C T R - -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
0x2 (Dec. by 50%)
0x3 (Dec. by 25%)
[PX][BX] Blue Channel
0-100%