InZennio Z41
http://www.zennio.com
Tecnical Support:
http://support.zennio.com
22
Note
:
although the DPT of this object considers a field for setting the day of
the week, Z41 calculates it from the date and therefore ignores that field
.
[General] Date
: 3-byte object for setting the internal date of the device, for
example, by linking it to a KNX clock. This object also allows read requests,
so the current date of the device can be checked. It is also automatically sent
after date changes made by the user from the screen itself.
[General] Scenes: send
: 1-byte object through which scene run/save orders
(1 to 64 according to the KNX standard) can be sent to the bus in case any of
the boxes is configured as a scene control or as a timer.
[General] Internal Temperature
: 2-byte object through which the value of
the current measurement of the built-in sensor will be sent to the bus,
according to the parameterisation (see section 3.2.4).
[General] Illumination
: 1-bit object that, upon the reception of the value “1”
from the bus, will bring the backlight of the screen to the maximum level,
while the reception of the value “0” will have no effect. This maximum
illumination will last for a certain time, according to the explanation in section
2.5.
[General] Touch Lock
: 1-bit object that, upon the reception of the value “1”
from the bus, will lock the touch panel so that user presses are ignored from
that moment. Touch locking will be interrupted as soon as the value “0” is
received through this object. See section 3.2.3.
During the parameter configuration, a screen similar to Figure 13 will be shown.
Figure 13
Parameter Screen shown by default
As shown in Figure 13, the parameter window is initially divided into four main tabs:
Main Configuration
, which contains a few more tabs: