AF6ZP0CA – COMBIAC0 & ACE0 2uC – User Manual
4.4 External
devices
4.4.1 Key
Input
KEY input (
A10
) is generally connected to the vehicle start key switch. It supplies
battery voltage to the logic circuitry and it also pre-charges the DC-link capacitors
at key-on, before the main contactor closes. The KEY voltage is monitored.
4
Note: external loads connected to the power teB, such as proximity
switches, load the internal PTC resistor along the key input path, with the
consequence that the pre-charge voltage may be lower than expected.
Protection
The KEY input is protected against reverse polarity with a diode and it has got
approximately 22 nF of capacitance to -B for ESD protection and other filtering
elements. This capacitance may give a high current spike at the KEY input
depending on the external circuit.
Fuse FU1 (see functional drawings, paragraph 3.2), should be sized according to
the number of motor controllers connected to it (10 A fuse is recommended) and
the current absorption of the KEY input (input power below 15 W).
U
The key switch connected to the KEY input must handle the short inrush
current spike to the ESD protection capacitors. The current peak depends
on the external circuit and wires.
U
Cables from the battery to the KEY input should be as short as possible
Connector position
A10
.
4.4.2 Digital
inputs
Digital inputs are meant to work in the voltage range from -B to +B. The related
command devices (microswitches) must be connected to +B (typically to the key
voltage) or to -B, depending on the input configuration (refer to pin description in
paragraph 4.2). Pull-down or pull-up resistors are built-in.
Functional devices (like FW, BW, PB, etc.) are normally open, so that each
associated function becomes active when the microswitch closes. Safety-related
devices (like CUTBACK) must be normally closed, so that each associated
function becomes active when the microswitch opens.
Nominal voltage figures for digital inputs in standard Zapi configuration are listed
in the following table. Custom hardware may feature different voltage values.
Содержание ACE0 2mC
Страница 13: ...AF6ZP0CA COMBIAC0 ACE0 2uC User Manual Page 13 155 3 2 Connection drawings 3 2 1 AC Traction configuration...
Страница 14: ...Page 14 155 AF6ZP0CA COMBIAC0 ACE0 2uC User Manual 3 2 2 AC Pump configuration...
Страница 15: ...AF6ZP0CA COMBIAC0 ACE0 2uC User Manual Page 15 155 3 2 3 AC CAN Open configuration...
Страница 16: ...Page 16 155 AF6ZP0CA COMBIAC0 ACE0 2uC User Manual 3 2 4 PMSM Traction configuration...
Страница 17: ...AF6ZP0CA COMBIAC0 ACE0 2uC User Manual Page 17 155 3 2 5 PMSM Pump configuration...
Страница 98: ...Page 98 155 AF6ZP0CA COMBIAC0 ACE0 2uC User Manual Torque curves...