AF6ZP0CA – COMBIAC0 & ACE0 2uC – User Manual
Page – 127/155
Troubleshooting:
Check in the HARDWARE SETTINGS list the value of those parameters.
VACC NOT OK
(MDI/LED code = 78)
Cause:
At key-on and immediately after that, the travel demands have been turned
off. This alarm occurs if the ACCELERATOR reading (in TESTER function) is
above the minimum value acquired during the PROGRAM VACC procedure.
Troubleshooting:
-
Check the wirings.
-
Check the mechanical calibration and the functionality of the accelerator
potentiometer.
-
Acquire the maximum and minimum potentiometer value through the
PROGRAM VACC function.
-
If the problem is not solved, replace the logic board.
VACC OUT RANGE
(MDI/LED code = 85)
Cause:
-
The CPOT input read by the microcontroller is not within the MIN VACC
÷ MAX VACC range, programmed through the PROGRAMM VACC
function (see paragraph 9.1).
-
The acquired values MIN VACC and MAX VACC are inconsistent.
Troubleshooting:
-
Acquire the maximum and minimum potentiometer values through the
PROGRAM VACC function. If the alarm is still present, check the
mechanical calibration and the functionality of the accelerator
potentiometer.
-
If the problem is not solved, replace the logic board.
VDC LINK OVERV.
(MDI/LED code = 77)
Cause
This fault is displayed when the controller detects an overvoltage condition.
Overvoltage threshold depends on the nominal voltage of the controller.
Nominal voltage
24V
36/48V
72/80V
96V
Overvoltage threshold
35V
65V
115V
130V
As soon as the fault occurs, power bridge and MC are opened. The condition
is triggered using the same HW interrupt used for undervoltage detection, uC
discerns between the two evaluating the voltage present across DC-link
capacitors:
- High
voltage
Overvoltage condition
- Low/normal
voltage
Undervoltage condition
Troubleshooting
If the alarm happens during the brake release, check the line contactor
contact and the battery power-cable connection.
VDC OFF SHORTED
(MDI/LED code = 88)
Cause
The logic board measures a voltage value across the DC-link that is
constantly out of range, above the maximum allowed value.
Содержание ACE0 2mC
Страница 13: ...AF6ZP0CA COMBIAC0 ACE0 2uC User Manual Page 13 155 3 2 Connection drawings 3 2 1 AC Traction configuration...
Страница 14: ...Page 14 155 AF6ZP0CA COMBIAC0 ACE0 2uC User Manual 3 2 2 AC Pump configuration...
Страница 15: ...AF6ZP0CA COMBIAC0 ACE0 2uC User Manual Page 15 155 3 2 3 AC CAN Open configuration...
Страница 16: ...Page 16 155 AF6ZP0CA COMBIAC0 ACE0 2uC User Manual 3 2 4 PMSM Traction configuration...
Страница 17: ...AF6ZP0CA COMBIAC0 ACE0 2uC User Manual Page 17 155 3 2 5 PMSM Pump configuration...
Страница 98: ...Page 98 155 AF6ZP0CA COMBIAC0 ACE0 2uC User Manual Torque curves...