2-6
<Toc>
<2. Initial Settings>
IM 05E01B02-41E
1st Edition : May 31,2000-00
■
Instrument Input Range Codes
Input
Type
Instrument Input
Range Code
Instrument
Input Range
Measurement Accuracy
OFF (0)
typeK1 (1)
-270.0 to 1370.0
°
C
-450.0 to 2500.0
⬚
F
Set the data item PV Input Type "IN1" to the OFF option to leave the PV input
type undefined.
typeK2 (2)
-270.0 to 1000.0
°
C
-450.0 to 2300.0
⬚
F
K
-200.0 to 500.0
°
C
-200.0 to 1000.0
⬚
F
J
typeJ (4)
-200.0 to 1200.0
°
C
-300.0 to 2300.0
⬚
F
typeT1 (5)
-270.0 to 400.0
°
C
-450.0 to 750.0
⬚
F
T
typeT2 (6)
0.0 to 400.0
°
C
-200.0 to 750.0
⬚
F
⫾
0.1% of instrument range
⫾
1 digit at 0
°
C or more
⫾
0.2%
⫾
1 digit for temperatures below 0
°
C,
where the accuracy is:
⫾
2% of instrument range
⫾
1
digit for temperatures below -200.0
°
C for a type-K thermo-
couple, or
⫾
1% of instrument range
⫾
1 digit for
temperatures below -200.0
°
C for a type-T thermocouple.
B
typeB (7)
0.0 to 1800.0
°
C
32 to 3300
⬚
F
⫾
0.15% of instrument range
⫾
1 digit at 400
°
C or more
⫾
5% of instrument range
⫾
1 digit at less than 400
°
C
S
typeS (8)
0.0 to 1700.0
°
C
32 to 3100
⬚
F
R
typeR (9)
0.0 to 1700.0
°
C
32 to 3100
⬚
F
⫾
0.15% of instrument range
⫾
1 digit
N
typeN (10)
-200.0 to 1300.0
°
C
-300.0 to 2400.0
⬚
F
⫾
0.1% of instrument range
⫾
1 digit
⫾
0.25% of instrument range
⫾
1 digit for temperatures
below 0
°
C
E
typeE (11)
-270.0 to 1000.0
°
C
-450.0 to 1800.0
⬚
F
L(DIN)
typeL (12)
-200.0 to 900.0
°
C
-300.0 to 1600.0
⬚
F
-200.0 to 400.0
°
C
-300.0 to 750.0
⬚
F
typeU1 (13)
U(DIN)
typeU2 (14)
0.0 to 400.0
°
C
-200.0 to 1000.0
⬚
F
⫾
0.1% of instrument range
⫾
1 digit at 0
°
C or more
⫾
0.2%
⫾
1 digit for temperatures below 0
°
C, where the
accuracy is:
⫾
1.5% of instrument range
⫾
1 digit for
temperatures below -200.0
°
C for a type-E thermocouple.
W typeW
(15)
0.0 to 2300.0
°
C
32 to 4200
⬚
F
⫾
0.2% of instrument range
⫾
1 digit
Platinel 2
Plati2 (16)
0.0 to 1390.0
°
C
32.0 to 2500.0
⬚
F
⫾
0.1% of instrument range
⫾
1 digit
PR20-40
PR2040 (17)
0.0 to 1900.0
°
C
32 to 3400
⬚
F
⫾
0.5% of instrument range
⫾
1 digit at 800
°
C or more
No accuracy is guaranteed at less than 800
°
C
Thermocouple
Unspecified
W97Re3-
W75Re25
W97Re3 (18)
0.0 to 2000.0
°
C
32 to 3600
⬚
F
⫾
0.2% of instrument range
⫾
1 digit
JPt1 (30)
-200.0 to 500.0
°
C
-300.0 to 1000.0
⬚
F
⫾
0.1% of instrument range
⫾
1 digit (Note 1) (Note 2)
JPt100
JPt2 (31)
-150.00 to 150.00
°
C
-200.0 to 300.0
⬚
F
⫾
0.2% of instrument range
⫾
1 digit (Note 1)
Pt1 (35)
-200.0 to 850.0
°
C
-300.0 to 1560.0
⬚
F
Pt2 (36)
-200.0 to 500.0
°
C
-300.0 to 1000.0
⬚
F
⫾
0.1% of instrument range
⫾
1 digit (Note 1) (Note 2)
RTD
Pt100
Pt3 (37)
-150.00 to 150.00
°
C
-200.0 to 300.0
⬚
F
⫾
0.2% of instrument range
⫾
1 digit (Note 1)
0.4 to 2 V
0.4 to 2 V (40)
Standard
signal
1 to 5 V
1 to 5 V (41)
0 to 2 V
0 to 2 V (50)
0 to 10 V
0 to 10 V (51)
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
-10 to 20 mV
mv 1 (55)
-10.00 to 20.00 mV
DC voltage
0 to 100 mV
mv 2 (56)
0.0 to 100.0 mV
⫾
0.1% of instrument range
⫾
1 digit
Display range is scalable in a range of -19999 to 30000.
Display span is 30000 or less.
typeK3 (3)
Numbers in ( ) are the setting value that apply when the
communication is used.
*
Performance in the standard operating conditions (at 23
⫾
2
⬚
C, 55
⫾
10%RH, and 50/60 Hz power frequency)
Note 1: The accuracy is
⫾
0.3
⬚
C of instrument range
⫾
1 digit for a temperature range from 0
⬚
C to 100
⬚
C.
Note 2: The accuracy is
⫾
0.5
⬚
C of instrument range
⫾
1 digit for a temperature range from -100
⬚
C to 200
⬚
C.
*
To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250
⍀
resistor. This resistor
is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)