4.11 Switching to Local-mode (LOCAL) Operation
The controller can be switched to local-mode operation when it is in program operation or in
a RESET mode.
The following operating procedure switches the controller to local-mode operation during
program operation.
1.
Bring the current display for program operation into view.
PV
SET/ENT
PT.No
RUN
RESET
DISP
MODE
PVE2
PVE1
PV2
TME
AL
1
1
2
3
4
MAN2
PRG
RST
HLD
LOC
MAN1
CAS
PTNO: 1
SEGNO: 1/ 3
RCY: 0/ 0
SP:
40.0
°
C
TM= 0h14
Indicates the controller is
running on segment 1.
PRG or RST
lamp ON.
2.
Press the
MODE
key several times to display the LOC:ON mode parameter.
PV
SET/ENT
PT.No
RUN
RESET
DISP
MODE
PVE2
PVE1
PV2
TME
AL
1
1
2
3
4
MAN2
PRG
RST
HLD
LOC
MAN1
CAS
MODE DISPLAY
#3
changing!
local drive switch
LOC
:
ON
Blinks during
change.
3.
Press the
SET/ENT
key once. The controller begins running with a local setpoint (L.SP).
The figure below shows an example of setting the controller with the local setpoint of 50.0°C.
PV
SET/ENT
PT.No
RUN
RESET
DISP
MODE
PVE2
PVE1
PV2
TME
AL
1
1
2
3
4
MAN2
PRG
RST
HLD
LOC
MAN1
CAS
PTNO: 1
SEGNO: 0/ 3
RCY: 0/ 0
SP:
50.0
°
C
TM=-------
The symbol “L.” represents
a local setpoint.
L.
LOC lamp
ON.