<6. Parameters>
6-7
IM 05E01B02-41E
■
Operating Parameters
●
Instrument Alarm Setting Parameters
Located in: Main menu =
AL
Instrument alarm-1
setpoint
Instrument alarm-2
setpoint
PV high limit/SP high
limit alarm: 100.0% of
PV input range
Deviation alarm: 0.0% of
PV input range span
Other PV/SP low limit
alarm: 0.0% of PV input range
Output high limit
alarm: 100.0%
Output low limit
alarm: 0.0%
Allows alarm action to be set irrespective of the
program.
PV alarm / SP alarm: -100.0 to 100.0% of
PV input range
Deviation alarm: -100.0 to 100.0% of PV
input range span
Output alarm: -5.0 to 105.0%
A1
A2
Parameter
Symbol
Target Item
in CD-ROM
Ref.3.4(1)
User
Setting
Name of Parameter
Setting Range and Description
Initial Value
Instrument alarm-3
setpoint
A3
Instrument alarm-4
setpoint
A4
●
Operation-related Parameters
Located in: Main menu =
LP1
; Submenu =
PAR
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User
Setting
Target Item
in CD-ROM
Ref.2.1(5)
Ref.2.1(6)
Ref.1.1(1)
Ref.3.4(4)
Ref.5.2(2)
Auto-tuning
OFF (0): No auto-tuning
1: Auto-tuning for 1st group of PID
2: Auto-tuning for 2nd group of PID
3: Auto-tuning for 3rd group of PID
4: Auto-tuning for 4th group of PID
5 to 8: Perform auto-tuning on a group basis in the same way as 1 to 4
9: Performs auto-tuning to all groups 1 to 8.
OFF (0)
PV input filter
OFF (0), 1 to 120 sec.
Used when the PV input value fluctuates.
OFF (0)
PV input bias
-100.0% to 100.0% of PV input range span
Used to correct the PV input value.
0.0% of PV
input range
span
1.0% of PV
input range
span
ON/OFF rate
detection band
ON/OFF rate
high limit
ON/OFF rate
low limit
0.0 to 100.0% of PV input range span
ORL + 1 digit to 105.0%
100.0%
-5.0% to ORH - 1 digit
0.0%
AT
SC
FL
BS
ORB
ORH
ORL
Starting time of
program pattern
operation
0.00 to 99.59 (“hour, minute” or “minute, second”)
The controller begins control when the specified time has
passed after power-on.
0.00
S.TM
“SUPER” function
OFF (0)
OFF (0): Disable
1: Overshoot suppressing function
Suppresses overshoots generated by abrupt changes in the
target setpoint or by disturbances.
2: Hunting suppressing function (Stable mode)
Suitable to stabilize the state of control when the load varies
greatly, or the target setpoint is changed.
Enables to answer the wider characteristic changes compared
with Response mode.
3: Hunting suppressing function (Response mode)
Enables quick follow-up and short converging time of PV for the
changed target setpoint.
Note: Use “SUPER” function (SC) 2 or 3 in PID control or PI control.
“SUPER” function 2 or 3 is not available in the following controls:
1) ON/OFF control
2) P control (control for proportional band only)
3) PD control (control for proportional band and derivative item only)
4) Heating/cooling control
Do not use hunting suppressing function when control processes
with response such as flow or pressure control.