<6. Parameters>
6-21
IM 05E01B02-41E
●
Input-related Parameters
Located in: Main menu =
UPMD
; Submenu =
IN
PV input type
(INPUT 1 terminals)
Terminals ,
and
Specify the type of PV input as a range code.
See “Instrument Input Range Codes” in “2. Initial Settings.”
OFF (0)
11 12
13
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User
Setting
Target Item
in CD-ROM
PV input unit
Select the unit of PV input.
% (0): Percent
- (2): No unit
C (1): Degree Celsius
F (5): Fahrenheit
IN1
IN2
Max. value of PV
input range
Set the instrument input range (RL1 < RH1).
- For temperature input -
Set the range of temperature that is actually controlled.
- For voltage input -
Set the range of a voltage signal that is applied.
The scale across which the voltage signal is actually controlled
should be set using the parameters Maximum Value of PV Input
Scale (SH1) and Minimum Value of PV Input Scale (SL1).
Depends on
the PV
input type.
Depends on
the PV
input type.
UNI1
RH1
Min. value of PV
input range
PV input decimal
point position
(shown when in
voltage-input mode)
Set the position of the decimal point of voltage-mode PV input.
0 to 4
0: No decimal place
1: One decimal place, 2 to 4: Two, three, four decimal places
Depends on
the PV
input type.
Depends on
the PV
input type.
RL1
Max. value of PV
input scale
(shown when in
voltage-input mode)
Set the read-out scale of voltage-mode PV input.
-19999 to 30000, where SL1 < SH1
SDP1
SH1
Min. value of PV
input scale
(shown when in
voltage-input mode)
Selection of PV
input burnout action
Allows the PV input value to be determined as shown below in
case of PV input burnout.
• 105% of PV input range if set to “Upscale”
• -5.0% of PV input range if set to “Downscale”
OFF (0): Disable
UP (1): Upscale
DOWN (2): Downscale
Depends on
the PV
input type.
SL1
Allows input compensation to be applied to thermocouple input.
OFF (0): Absent
ON (1): Present
ON (1)
BSL1
RJC1
Presence/absence
of PV input
reference junction
compensation
Although not used in single-loop control, it is shown on the display.
UNI2
Although not used in single-loop control, it is shown on the display.
RH2
Although not used in single-loop control, it is shown on the display.
RL2
Although not used in single-loop control, it is shown on the display.
SDP2
Although not used in single-loop control, it is shown on the display.
SH2
Although not used in single-loop control, it is shown on the display.
SL2
Although not used in single-loop control, it is shown on the display.
BSL2
Although not used in single-loop control, it is shown on the display.
RJC2
Although not used in single-loop control, it is shown on the display.
1st Edition : May 31,2000-00