<3. Programming>
3-5
IM 05E01B02-41E
4.
Press the
key once to display the
submenu “PRG”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
programming
main menu
PRG
5.
Press the
SET/ENT
key once to display the
Pattern Number parameter “PTN”. At this
point, the PV display shows “001.00” (the
first three digits denote the pattern number
and the last two digits the segment num-
ber).
SET/ENT
PT.No
RUN
RESET
DISP
MODE
MENU:PROG/PRG
#1
PTno.input
PTN
=
1
PV Display
6.
Press the
SET/ENT
key once to display the
Segment Number parameter “SEG”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
MENU:PROG/PRG
#2
SEGno. input
SEG
=
0
7.
Press the
SET/ENT
key once to display the
Starting Target Setpoint parameter “SSP1”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
MENU:PROG/PRG
#3
start set point 1
SSP1
=
0.0
°
C
1st Edition : May 31,2000-00
8.
Press the
or
key to display the
required setpoint.
The figure below shows an example of the
parameter set to “25.0
⬚
C”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
MENU:PROG/PRG
#3
changing!
start set point 1
SSP1
=
25.0
°
C
9.
Press the
SET/ENT
key once to register the
setpoint.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
MENU:PROG/PRG
#3
start set point 1
SSP1
=
25.0
°
C
10.
Press the
SET/ENT
key once to display the Start
Code parameter “STC”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
MENU:PROG/PRG
#5
start code select
STC
=
0
11.
Press the
SET/ENT
key once to display the
Target Setpoint parameter “TSP1” for
segment 1. At this point, the PV display
shows “001.01” (the first three digits
denote the pattern number and the last two
digits the segment number).
SET/ENT
PT.No
RUN
RESET
DISP
MODE
MENU:PROG/PRG
#24
target set point 1
TSP1
=
25.0
°
C
PV Display