IM 12A06S01-00EN-P
14
2 WIRING AND INSTALLATION
Figure 2.1: Installation diagram SA11
2.1 Installation site
The SA11 is weatherproof and can be installed both inside and outside. Select an
installation site that meets the following conditions:
• Mechanical vibrations and shocks are negligible
• No relay switch and power switch are installed close to the device
• There is space mounting the device to the Yokogawa sensor & Yokogawa HOST system
• Not exposed to direct sunlight or severe weather conditions
• Maintenance is possible
• No corrosive atmosphere
• Water Protection: IP67, NEMA Type 4X
2.2 Connecting to the sensor
2.2.1 Direct mounting
The SA11 can be installed directly on top of the Yokogawa labelled sensor by means of the
Variopin connection system. In this case the temperature limit of the device is determined by
the process temperature, limited from -30 up to +100°C / -22 up to +212°F for power supply
+2.7 to +4.5VDC, -30 up to +125°C / -22 up to +257°F for power 4.5 to +5.5VDC.
Figure 2.2: Example of direct mounting of SA11 to sensor
CAUTION
Place the Variopin connectors securely to guarantee IP67.
YPA Europe
Made in the Netherlands 3825HD-2
BA11
ACTIVE JUNCTION BOX
BUS
SENSOR CONNECTIONS
IN
OUT
J1
J2
J3
J4
WU11-M9-**-CN-S
Modbus Host
e.g. FLXA402
WU11-M9-**-WP-S
WU11-M9-**-WP-S
max. 100m (328ft)
max. 100m
(328ft)
max. 100m
(328ft)
Suffix
-C-AA-M9
Serial#
N3T400171
Power
+2.7. +5.5VDC/30mW
T amb.
-20.. + 55ºC
IP
Type 4X / IP66
2018
Read IM
12B06W03-01E-E