4. Installation Specifications
4-1
TI 33Q01J10-01E
4.
Installation Specifications
This section summarizes power consumption, in-rush current, breaker ratings, parts
durability and other data for the installation of CS 3000 system.
Electrical Specifications
Power consumption (current) and other electrical data are shown below:
Table Electrical Specifications (1/3)
Equipment
Input-voltage range
Max. power
consumption
(VA, A) (*1)
Heating
value J/h
(*2)
Voltage (V AC) Frequency (Hz)
Reference value
LPCKIT Enclosed Display Style Console Type HIS
LCD Single Stacked (built in General Purpose PC)
(*3)
100-120
50/60±3
520 VA
1370 × 10
3
(380 W)
220-240
550 VA
Reference value
LPCKIT Enclosed Display Style Console Type HIS
LCD Dual Stacked (built in General Purpose PC) (*3)
100-120
50/60±3
590 VA
1620 × 10
3
(450 W)
220-240
630 VA
Reference value
YPCKIT Open Display Style Console Type HIS
LCD Single Stacked
(built in General Purpose PC) (*3)
100-120
50/60±3
560 VA
1370 × 10
3
(380 W)
220-240
590 VA
Reference value
YPCKIT Opened Display Style Console Type HIS
LCD Dual Stacked
(built in General Purpose PC) (*3)
100-120
50/60±3
670 VA
1550 × 10
3
(430 W)
220-240
720 VA
AFS10S, AFG10S 19-inch Rack Mountable Type
(excluding node)
Field Control Unit
100-120
50/60±3
250 VA
432 × 10
3
(120 W)
220-240
250 VA
24 V DC
4.5 A
AFS10D, AFG10D 19-inch Rack Mountable Type
(excluding node)
Duplexed Field Control Unit
100-120
50/60±3
400 VA
720 × 10
3
(200 W)
220-240
410 VA
24 V DC
8 A
AFS20S, AFG20S With Cabinet (excluding node)
Field Control Unit
100-120
50/60±3
300 VA
540 × 10
3
(150 W)
220-240
330 VA
24 V DC
6 A
AFS20D, AFG20D With Cabinet (excluding node)
Duplexed Field Control Unit
100-120
50/60±3
450 VA
828 × 10
3
(230 W)
220-240
480 VA
24 V DC
10 A
AFS20S, AFG20S With Cabinet (including node)
Field Control Unit
100-120
50/60±3
1700 VA
3960 × 10
3
(1100 W)
220-240
2000 VA
24 V DC
50 A
AFS20D, AFG20D With Cabinet (including node)
Duplexed Field Control Unit
100-120
50/60±3
1700 VA
3960 × 10
3
(1100 W)
220-240
2000 VA
24 V DC
50 A
*1:
Power consumption in steady operation is indicated in VA (AC) or A (DC). When power consumption varies according to the installed number
of equipment, power consumption by the maximum number of units installed is listed.
*2:
Heating value in steady operation is indicated in Joule/hour. When heating value varies according to the installed number of equipment,
heating value by the maximum number of units installed is listed.
*3:
The value obtained on the premise that the maximum power consumption of built-in PC is 400 VA. The service outlet is not included.
Sep. 30, 2008-00