1. System Installation Requirements
1-18
TI 33Q01J10-01E
Cabling
Observe the following when cabling the power unit to the CS 3000 system equipment:
• Protect signal cables from induced noise.
• Protect signal cables from induction from high-voltage power lines.
• Separate the CS 3000 system power supply from other equipment power supplies-use a
separate power distribution board.
• Provide a dedicated breaker for each power supply. Install breakers and devices they
control they control in the same room.
• As far as possible install power supply cables and high-voltage power lines in metallic
conduits.
• Use shielded cables if metallic conduits cannot be provided.