1. System Installation Requirements
1-9
TI 33Q01J10-01E
EMC Conformity Standards (*1)
[CE Marking] EMC Directive
EN 55011 Class A Group1 (*2)
EN 61000-6-2 (*3)
EN 61000-3-2 (*4)
EN 61000-3-3 (*5)
[C-Tick Marking]
EN 55011 Class A Group1 (*2)
Standards for Hazardous Location Equipment
[CSA Non-Incendive] (*6)
Class I, Division 2, Groups A, B, C and D Temperature code T4
CSA Standard C22.2 No.157-92
CSA Standard C22.2 No.213-M1987
ISA Standard ISA-S12.12 1994 (for 100-120 V AC and 24 V DC power supply)
[FM Non-Incendive] (*7)
Class I, Division 2, Groups A, B, C and D Temperature code T4
FM Class Number 3600:1998
FM Class Number 3611:2004
FM Class Number 3810:2005
(for 100-120 V AC, 220-240 V AC and 24 V DC power supply)
[Type n] (*8)
EN 60079-15:2005
IEC 60079-0:2004
IEC 60079-11:1999
(for 24 V DC power supply)
[Intrinsic Safety]
EN 50014:1997 +A1 +A2
EN 50020:1994
EN 50021:1999
*1: To conform to the safety standards and the EMC conformity standards, install the 19-inch rack mountable type devices in a
keyed metallic cabinet.
*2:
A Class A hardware device is designed for use in the industrial environment. Please use this device in the industrial environment
only.
*3: A lightening arrester or the like is required to meet this surge immunity standard.
*4: An external device such as a power unit with harmonic current neutralizer and an active harmonics conditioner must be
connected to meet this harmonic current emission standard. See Section 1.3 “Power Supply System”.
*5: The specified limits of voltage drop across wiring must be satisfied to meet this standard. For the selection of the power cables
and their wiring, refer to Section 3.2 “Connecting Power”.
*6: To meet a standard for hazardous location equipment, the 19-inch rack-mounted devices must be installed in a keyed metallic
cabinet approved by CSA or non-incendive regulator in your area.
*7:
To meet a standard for hazardous location equipment, the 19-inch rack-mounted devices must be installed in a keyed metallic
cabinet approved by FM or non-incendive regulator in your area.
*8:
To be compatible with Type n, the specification requirements of EN 61010-1 and EN 60079-15 must be met, and a keyed metallic
cabinet, whose degree of protection is IP54 or above, prescribed by IEC 60529 must be used for housing.
Note: According to the New Approach Directive, the manufacturer and the representative office in EU are indicated below.
Manufacturer : YOKOGAWA Electric Corporation (2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, Japan).
Representative office in EU Community : Yokogawa Europe B.V. (Euroweg 2, 3825 HD Amersfoort, The Netherlands).
Feb. 1, 2009-00