3. Cabling
3-87
TI 33Q01J10-01E
3.7.12
Connecting Signal Cables with PROFIBUS
Communication Module ACP71
F030729.ai
Figure PROFIBUS Communication Module ACP71
Use shielded twisted-pair cables for PROFIBUS.
Table PROFIBUS Interface Connector Pin Positions
Pin position
Signal
Description
1
Shield
2
N.C.
3
A-Line
I/O data
4
CNTR-P
Repeater Control Signal
5
D-GND
6
VP
+5V
7
N.C.
8
B-Line
I/O data
9
N.C.
May 18, 2007-00